Table 36: UL conformity declaration information
Information
Description
Purpose of control
Sensing control or operating control
Construction of
control
Electronic, independently mounted control that you mount in or on a
remote panel
Compressor relay: 100,000 cycles
Defrost relay: 30,000 cycles
Evaporator fan or auxiliary relays: 30,000 cycles
Number of cycles
Alarm relay: 6,000 cycles
Method of mounting
control
Flush mount into refrigeration panel opening: 71 mm (2.8 in.) x 29 mm
(1.14 in.)
Degree of IP
protection
Gasket sealed; IP54 category 2
Disconnection type
Alarm relay: SPDT micro-disconnection type 1.B
Compressor relay: SPST micro-interruption type 1.C
Evaporator fan or Auxiliary relay: SPST micro-disconnection type 1.B
Type action
Defrost relay: SPST micro-disconnection type 1.B
Heat and fire
resistance category
D
Rated impulse
voltage
2500 V
Over voltage
category
II
Pollution degree
4 front face, 2 back housing
Table 37: ADPT-MR5-RS485 Network Communciation Adapter technical specifications
Information
Description
Product
ADPT-MR5-RS485
Ambient conditions
• Operating: -32°C to 60°C (-25°F to 140°F), 0% to 95% RH noncondensing
• Shipping and storage: -40°C to 85°C (-40°F to 185°F), 0% to 95% RH
noncondensing
Baud rate
• 9.6K bits per second, 19.2K bits per second, 38.4K bits per second
• Default: 38.4K bits per second
Parity
None
Dimensions
(H x W x D)
72 mm (2.83 in.) x 34 mm (1.34 in.) x 23mm (0.91 in.)
Weight
~33.56 grams (0.074 lb)
Compliance
North America:
United States: UL Listed SDFY.SA516, FCC Compliant to CFR47, Part 15,
Subpart B, Class B limits
Canada: cUL Listed SDFY7.SA516, Industry Canada (IC) compliant to
Canadian ICES-003, Class B limits
MR5 Series Panel Mount Case Controller Technical Bulletin
68