Setting up the defrost parameters
To enter the defrost setup menu, navigate to the high-level
DEFROST SETUP
screen and press
SET
.
To move through the defrost setup screens and options, press
DOWN
and
UP
.
Figure 15: Defrost cycle setup screens navigation map
Table 15: Defrost cycle setup screens descriptions, values, and selections
Screen name
Description
Value or
selection
To set the maximum defrost duration time, press
SET
.
n/a
DEFROST
DURATION
Select the maximum defrost duration value from the range 0
min to 99 min and press
SET
.
Note:
Regardless of the termination type, all defrost cycles
terminate when the system reaches the defrost duration
value.
0 min to 99 min
To set the drip time delay, press
SET
.
n/a
DRIP TIME
Conditional
screen
Select the drip time delay value from the range 0 min to 10
min and press
SET
.
0 min to 10 min
To set the defrost termination temperature, press
SET
.
n/a
DEFROST
TERMINATION
TEMPERATURE
Conditional
screen
Select the defrost termination temperature value from the
range -1°C to 32°C (30°F to 90°F) and press
SET
.
Note:
The
DEFROST TERMINATION TEMPERATURE
screen displays only if
TE-MP
is selected on the
DEFROST
TERM TYPE
screen in the system setup menus.
-1°C to 32°C
(30°F to 90°F)