Table 29: MR5 BACnet objects available on Verasys or standard BACnet
Name
Object
type/
instance
Enum set/range
Read (R)/
write (W)
Alarm supported
QREV/PSHC : Refrigerant MV10290
Refrigerant type:
1-R410A
2-R404
3-R407A
4-R134A
5-Reserved
6-R22
7-R407C
8-R_407F
9-R_417A
10-R_422A
11-R_422D
12-R_427A
13-R_438A
14-R_448A
15-R_449A
16-R_450A
17-R_507A
18-R_513A
19-Unknown
20-Unknown
21-Unknown
R
Binary Input 1 : State
BI10020
Binary Input status:
0 - Open
1 - Close
R
Binary Input 2 : State
BI10416
Binary Input status:
0 - Open
1 - Close
R
Binary Input 1 : Mode
MV10461
1 - None
2 - Refrigerant Leak
3 - Door Open
R
Binary Input 2 : Mode
MV10455
1 - None
2 - Refrigerant Leak
3 - Door Open
R
Auto DST
MV10389
1 - No
2 - Yes
R
Relay Selection
MV10371
1 - Fan
2 - Auxiliary
R
SetPoint
AV10321
-40°F to 122°F
(-40°C to 50°C)
W
Differential
AV10329
1°F to 15°F
(1°C to 8°C)
W
MR5 Series Panel Mount Case Controller Technical Bulletin
62
Discontinued