![Paul CLIMOS F 200 Original Operating Instructions Download Page 54](http://html1.mh-extra.com/html/paul/climos-f-200/climos-f-200_original-operating-instructions_4022625054.webp)
54
Error sensor 4
Sensor break or short circuit
temperature sensor T4
Check or replace sensor
Supply air temperature too
low
Minimum supply air temperature <
setpoint;
Supply air temperature > setpoint
+ 1 K
Intake air temperature too
low
Current intake air temperature <
setpoint; longer than 30 minutes
Intake air temp > setpoint; control
after 1 h
Error fan 1 Hall
Supply fan speed does not report
manual adjustment of fan speed
Error fan 2 Hall
Exhaust fan speed does not
report
manual adjustment of fan speed
BUS version incompatible
Software versions of the
components not compatible
Replace software versions
Too many devices connected Too many components connected
to the BUS
Remove surplus components
Fan slave not connected
Lack of BUS-communication
Fan slave connected
Communication error
fan slave
Lack of BUS-communication
Check BUS-communication
Communication error
defroster
Lack of BUS-communication
Check BUS-communication
Communication error
heater battery
Lack of BUS-communication
Check BUS-communication
Communication error
flap of the geothermal heat
exchanger
Lack of BUS-communication
Check BUS-communication
Communication error
general
Lack of BUS-communication
Disconnection from power supply,
then restart
Heating does not switch off
Error BUS-thermostat
Replace BUS-thermostat
General control unit error
Lack of BUS-communication with
control unit
Check BUS-communication
Tab. 39: Overview visualisation of errors and error treatment with TFT touch panel
Summary of Contents for CLIMOS F 200
Page 1: ...Version 2 0_06 2016 EN...
Page 57: ...57 Dimensional sketch 3 9 4 Fig 55 Dimension drawing HRU CLIMOS...
Page 58: ...58 Circuit diagram CLIMOS Basic series 3 9 5 Fig 56 Terminal assignment CLIMOS Basic...
Page 59: ...59 Circuit diagram CLIMOS Comfort series 3 9 6 Fig 57 Terminal assignment CLIMOS Comfort...
Page 60: ...60 Terminal scheme master controller 3 9 7 Fig 58 Terminal assignment Master Controller...
Page 65: ...65 Product fiche 4 5...