21
parameterized between 17 % and 100 %. Using the navigation buttons, the characteristic variables (red
background of the text) to be parameterised can be selected and the values can be set using the buttons
+ / -.
Symbol Designation
Output signal sensor
0 … 10 V characteristic curve
4 … 20 mA characteristic curve
Characteristic
curve start
value
Umin (V)
ԑ
n_min (%)
Imin (mA)
ԑ
n_min (%)
Characteristic
curve end
value
Umax (V)
ؙ
n_max (%)
Imax (mA)
ԑ
n_max (%)
U-n- Characteristic curve graph
I-n- Characteristic curve graph
Tab. 11: Parameterization automatic sensor
Plausibility check for sensors with current output:
•
Concerns the analogue input on the master controller (configuration as 4…20 mA input)
•
Error message if a value of 0… 3 mA is applied at the input for more than 1 s
•
Reset error if I > 3.5 mA for at least 1 s
2.3.2.5 Submenu
Date/Time
In this menu, date and time are set. Using the navigation buttons, the characteristic variables (red
background of the text) to be parameterised can be selected and the values can be set using the buttons
+ /-.
2.3.2.6 Submenu Choose language
In this menu, the language for the TFT touch panel can be selected with the navigation buttons.
2.3.2.7 Submenu Screen dimming
In this menu, an individual screen brightness and the duration until the occurrence of dimming after non-
operation can be set using the navigation buttons.
•
Duration until dimming in 1 min-steps
•
Dimming in 5 %-steps
Symbol
Designation
Explanation / actions
Duration until
dimming
Settings: 1 min …10 min,
until activation of dimming after last operation of the TFT touch
panel
Degree of
dimming
Settings: 5 % …95 %,
relating to the basic brightness when the screen is active
Button
Light bulb
Using this button, the set dimming can be tested. The screen is
dimmed for 5 seconds according to setting.
Tab. 12: Parameterization screen dimming
Summary of Contents for CLIMOS F 200
Page 1: ...Version 2 0_06 2016 EN...
Page 57: ...57 Dimensional sketch 3 9 4 Fig 55 Dimension drawing HRU CLIMOS...
Page 58: ...58 Circuit diagram CLIMOS Basic series 3 9 5 Fig 56 Terminal assignment CLIMOS Basic...
Page 59: ...59 Circuit diagram CLIMOS Comfort series 3 9 6 Fig 57 Terminal assignment CLIMOS Comfort...
Page 60: ...60 Terminal scheme master controller 3 9 7 Fig 58 Terminal assignment Master Controller...
Page 65: ...65 Product fiche 4 5...