3.4.5.2 Connection of external sensors
The operating mode
Automatic sensor
auf the automatic mode is controlled by an analogue sensor
signal which is generated by one or more sensors. The connection between the sensor module and the
terminal2 of the master controller is established by means of the cable prescribed for the transmission of
the sensor signal.
Terminal X2 master controller
Wire cable sensor module
X2.7 (analogue input1)
Wire 1 (sensor signal 0…10 V or 4…20 mA)
X2.8 (GND)
Wire 2 (GND)
Tab. 23: Terminal assignment connection analogue sensor signal
3.4.5.3 Connection
status
relay
A status relay on the master controller indicates the operating status of the fans (factory setting).
Fan off:
Contacts open
Fan on:
Contacts closed
Terminal X1 master controller
Contact designation
X1.9
Normally open contact status relay (max. 24 V switching voltage)
X1.10
Change over contact status relay (max. 24 V switching voltage)
Tab. 24: Terminal assignment connection status relay
3.4.5.4 Connection external release
The operation of the system can be released or locked by an external release signal. The potential-free
release contacts are on terminal X1 master controller and are bridged by the factory.
Terminal X1 master controller
Contact designation
X1.14
External release
X1.15
External release (GND)
Tab. 25: Terminal assignment connection external release
In case of removal of the bridge and no external release, the following visualisations are generated:
TFT touch panel
LED control panel
L1 and L7 light up
Tab. 26: Visualization no external release
Connection digital inputs or outputs
3.4.6
The digital inputs or outputs DIO1 and DIO2 can only be programmed with the configuration software.
The following parameterisations are set by the factory:
DIO1: Activate automatic mode (as digital input signal)
DIO2: Message in general (as digital output signal)
Summary of Contents for CLIMOS F 200
Page 1: ...Version 2 0_06 2016 EN...
Page 57: ...57 Dimensional sketch 3 9 4 Fig 55 Dimension drawing HRU CLIMOS...
Page 58: ...58 Circuit diagram CLIMOS Basic series 3 9 5 Fig 56 Terminal assignment CLIMOS Basic...
Page 59: ...59 Circuit diagram CLIMOS Comfort series 3 9 6 Fig 57 Terminal assignment CLIMOS Comfort...
Page 60: ...60 Terminal scheme master controller 3 9 7 Fig 58 Terminal assignment Master Controller...
Page 65: ...65 Product fiche 4 5...