23
Abbreviation
Designation
Explanation / actions
t_out_max Maximum
outside
temperature
Setting range upper threshold: 15 °C…30 °C
If the outside temperature is above the set threshold value, the
flap of the geothermal heat exchanger opens the intake air duct
for cooling the outside air.
→
cooling function
t_out_min Minimum
outside
temperature
Setting range lower threshold: -10 °C…14.5 °C
If the outside temperature is below the set threshold value, the
flap of the geothermal heat exchanger opens the intake air duct
for heating the outside air.
→
frost protection function
Tab. 15: Parameterization temperature thresholds flap of the geothermal heat exchanger
2.3.2.12 Submenu Brine loop cooling
Only for the CLIMOS F 200 Basic series without integrated defroster!
In this menu, an optionally available brine defroster is displayed. The cooling function of the brine
defroster can be activated or deactivated. The release of the brine defroster is selected using the
navigation buttons (red background of the text) and by setting the checkmark, and is confirmed with
Enter. Furthermore, the temperature threshold for the cooling function can be selected using the
navigation buttons (red background of the text) and can be set using the b / -.
Abbreviation
Designation
Explanation / actions
t_bde Threshold
temperature
brine defroster
Setting range: 15 °C…30 °C
If the outside temperature is above the set threshold value,
the brine defroster is activated for cooling the intake air.
→
cooling function
Tab. 16: Parameterisation temperature threshold brine defroster
Boost ventilation mode with external boost ventilation sensing device
2.3.3
In most cases, boost ventilation sensing devices e. g. switches or hygrostats are mounted in exhaust air
rooms such as bathrooms, W.C.s or kitchens in order to activate temporary maximum ventilation in these
rooms for fast discharge of increased moisture and odours.
When operating this control element, the functional properties and visualisations described for the boost
ventilation mode with LED control panel or TFT touch panel are generated. The boost ventilation mode is
started again at each activation and interrupts the current operating mode for the duration set. Following
this, the device switches back to the previously active operating mode. Manually switching the operating
mode by means of connected control panels stops the boost ventilation function.
Maintenance by the operator
2.4
Maintenance of the ventilation device and plant by the operator is limited to the periodic change of the
filters and cleaning of the supply and exhaust air valves. The filter must be checked every 3 months and
changed if necessary, however, at least every 6 months.
In this context, also check other filters available inside the ventilation plant and change them if necessary.
A replacement or cleaning of the filter mats at the exhaust air valves (e.g. bathroom, kitchen, W.C.s)
should be carried out every 2 – 3 months or at your own discretion when checking the degree of soiling.
If maintenance work is not carried out regularly, this impairs the functioning of the comfort
ventilation in the long term!
Summary of Contents for CLIMOS F 200
Page 1: ...Version 2 0_06 2016 EN...
Page 57: ...57 Dimensional sketch 3 9 4 Fig 55 Dimension drawing HRU CLIMOS...
Page 58: ...58 Circuit diagram CLIMOS Basic series 3 9 5 Fig 56 Terminal assignment CLIMOS Basic...
Page 59: ...59 Circuit diagram CLIMOS Comfort series 3 9 6 Fig 57 Terminal assignment CLIMOS Comfort...
Page 60: ...60 Terminal scheme master controller 3 9 7 Fig 58 Terminal assignment Master Controller...
Page 65: ...65 Product fiche 4 5...