Visualisation of errors and error treatment
3.8
The device control is equipped with an internal system for error detection.. The visualisation of the error
messages and the error forecast is made according to the display possibilities of the connected control
panel.
In response to an error condition, the fans are switched off.
Error signalling by means of the LED control panel
3.8.1
The visualisation of errors with the LED-control panel is carried out on the basis of 2.2.1.2. In addition to
the signalling of the error conditions, an LED coding, which does binary present the meaning of the error,
is generated by means of the LEDs L1…L7. Information on checking / measures for a possible
elimination of the error condition are given in Tab. 39.
The following LED-combinations for the display of the error coding marked with “x” apply:
LED combinations
Error message
Possible cause
L1 L2 L3 L4 L5 L6 L7
x
x
Supply air temperature too low
Supply air temperature <
setpoint
x
x
x
x
x
BUS version incompatible
Software versions of the
components not compatible
x
x
x
x
Too many devices connected
Too many components
connected to the BUS
x
x
x
x
x
Fan slave not connected
Lack of BUS-communication
x
x
x
x
x
Communication error of the fan
slave
Lack of BUS-communication
x
x
x
x
x
x
Communication error of the
defroster
Lack of BUS-communication
x
x
Communication error of the
heater battery
Lack of BUS-communication
x
x
x
Comm. error flap of the
geothermal heat exchanger
Lack of BUS-communication
x
x
x
Comm. error general
Lack of BUS-communication
x
x
x
x
Heating does not switch off
Error BUS-thermostat
x
x
x
General control unit error
Lack of BUS-communication
with control unit
Tab. 38: Overview binary error coding with LED-control panel
Visualisation of errors with the TFT touch panel
3.8.2
The visualisation of errors with the TFT touch panel is done in the plain text display of the error message.
In the main menu Information / Last message, the last three errors that occurred are registered in
compliance with the event with date and time. In addition to this display, a yellow warning triangle flashes
in the upper right edge of the screen.
The following plain text displays of the error message are visualised:
Message on display
Possible cause
Control / Action
Error sensor 1
Sensor break or short circuit
temperature sensor T1
Check or replace sensor
Error sensor 2
Sensor break or short circuit
temperature sensor T2
Check or replace sensor
Error sensor 3
Sensor break or short circuit
temperature sensor T3
Check or replace sensor
Summary of Contents for CLIMOS F 200
Page 1: ...Version 2 0_06 2016 EN...
Page 57: ...57 Dimensional sketch 3 9 4 Fig 55 Dimension drawing HRU CLIMOS...
Page 58: ...58 Circuit diagram CLIMOS Basic series 3 9 5 Fig 56 Terminal assignment CLIMOS Basic...
Page 59: ...59 Circuit diagram CLIMOS Comfort series 3 9 6 Fig 57 Terminal assignment CLIMOS Comfort...
Page 60: ...60 Terminal scheme master controller 3 9 7 Fig 58 Terminal assignment Master Controller...
Page 65: ...65 Product fiche 4 5...