EVO Installation Guide
129
12. Zone definition options
a.
‘Delay alarm transmission’ enabled by default for all zones.
b.
‘Force zone’ disabled by default for all zones.
13. Auto Zone Shutdown Counter Section [712] = 1 (CP-01 default)
a.
Section [3114] = 2 (CP-01 maximum 6)
b.
Section [3214] = 2 (CP-01 maximum 6)
c.
Section [3314] = 2 (CP-01 maximum 6)
d.
Section [3414] = 2 (CP-01 maximum 6)
e.
Section [3514] = 2 (CP-01 maximum 6)
f.
Section [3614] = 2 (CP-01 maximum 6)
g.
Section [3714] = 2 (CP-01 maximum 6)
h.
Section [3814] = 2 (CP-01 maximum 6)
14. Partition options : enabled : Switch to stay arming if no zone entry delay is opened
a.
Section [3121] option 1 enabled
b.
Section [3221] option 2 enabled
c.
Section [3321] option 3 enabled
d.
Section [3421] option 4 enabled
e.
Section [3521] option 5 enabled
f.
Section [3621] option 6 enabled
g.
Section [3721] option 7 enabled
h.
Section [3821] option 8 enabled
15. Arming/Disarming options : Exit delay termination
a.
Section [3122] option 4 disabled
b.
Section [3222] option 4 disabled
c.
Section [3322] option 4 disabled
d.
Section [3422] option 4 disabled
e.
Section [3522] option 4 disabled
f.
Section [3622] option 4 disabled
g.
Section [3722] option 4 disabled
h.
Section [3822] option 4 disabled
ADD THESE NOTES TO THE INSTALLER MANUAL
16. At the beginning of the manual.
a.
To comply with CP-01 standards, your system must be setup like this:
i
All system keypads must be audible (Mute disabled).
ii
A minimum of 2 must be installed to comply with CP-01 standards.
iii
To be CP-01, remote panic action shall be programmed on combined button only ( ).
17. Recent closing delay.
a.
If the option CP-01 is enabled (section [3028] opt 3), the recent closing delay will always be set to 120 sec and will not take care of the
programmed value.
18. Delay Alarm Transmission:
a.
In accordance with UL standards, the Abort Window standard intends that the aggregate of the Entry Delay and Abort Window will not be
programmed to exceed one minute.
b.
Non-effective on fire zones
19. Auto zone shutdown.
a.
Auto zone shutdown counter is reset every 48 hours of no movement.
20. Intellizone
a.
Sections [400] : Zones [001] to [192]
Option [7] OFF = Intellizone Disabled (default)
Option [7] ON = Intellizone Enabled for Selected Zone
This feature reduces the possibility of false alarms. When a zone with the Intellizone option opens, the panel does not immediately generate an
alarm. First it triggers the Intellizone Delay Timer. To program the Intellizone Delay Timer, key in the desired 3-digit value (000 to 255 seconds,
Default = 48 seconds) into section [3x10]( x = 1-8). If any of the following conditions occur during this period, the panel will generate an alarm:
• During the Intellizone Delay, a second zone has caused an alarm.
• During the Intellizone Delay, the zone in alarm has restored (closed) and re-occurred (opened). (Area options section [3x26](x=1-8) option 2 must
be disabled)
• The zone in alarm remains open for the entire Intellizone Delay. (Area options section [3x26](x=1-8) option 2 must be disabled)
21. Zone input specifications
a.
Maximum loop current (shorted loop): 2.2 mA
b.
Maximum loop voltage (open loop): 5.0 VDC
Summary of Contents for Digiplex EVO192
Page 1: ...Fire and Burglary Alarm System EVO192 Installation Guide...
Page 10: ...10 EVO Installation Guide...
Page 65: ...EVO Installation Guide 65 Event Reporting 10...
Page 125: ...EVO Installation Guide 125 Appendix F EVO192 CP 01 Implications as of June 13th 2014...
Page 136: ...136 EVO Installation Guide Notes...
Page 137: ...EVO Installation Guide 137...
Page 138: ...138 EVO Installation Guide...
Page 139: ...EVO Installation Guide 139...
Page 140: ...140 EVO Installation Guide Printed in Canada 10 2007 paradox com...
Page 147: ...paradox com EVO192 EI04...