20
EVO Installation Guide
Note:
The minimum permissible wire size to be employed shall be not smaller than No. 22 AWG (0.32 mm2).
Table 2: Milliamps (mA) Limitations For Each Run of Wire
Gauge: 18AWG
,
Surface: 0.823mm
2
Gauge: 22AWG
,
Surface: 0.326mm
2
Gauge: 24AWG
,
Surface: 0.205mm
2
Length of each
run of wire
Available
milliamps (mA)
Length of each
run of wire
Available
milliamps (mA)
Length of each
run of wire
Available
milliamps (mA)
30m(100ft.)
700
30m(100ft.)
700
30m(100ft.)
700
61m(200ft.)
700
61m(200ft.)
682
61m(200ft.)
429
91m(300ft.)
700
91m(300ft.)
454
91m(300ft.)
286
122m(400ft.)
700
122m(400ft.)
341
122m(400ft.)
214
152m(500ft.)
690
152m(500ft.)
273
152m(500ft.)
171
183m(600ft.)
575
183m(600ft.)
227
183m(600ft.)
143
213m(700ft.)
493
213m(700ft.)
195
244m(800ft.)
431
244m(800ft.)
170
274m(900ft.)
383
274m(900ft.)
151
305m(1000ft.)
345
305m(1000ft.)
136
457m(1500ft.)
230
610m(2000ft.)
172
762m(2500ft.)
138
914m(3000ft.)
115
Summary of Contents for Digiplex EVO192
Page 1: ...Fire and Burglary Alarm System EVO192 Installation Guide...
Page 10: ...10 EVO Installation Guide...
Page 65: ...EVO Installation Guide 65 Event Reporting 10...
Page 125: ...EVO Installation Guide 125 Appendix F EVO192 CP 01 Implications as of June 13th 2014...
Page 136: ...136 EVO Installation Guide Notes...
Page 137: ...EVO Installation Guide 137...
Page 138: ...138 EVO Installation Guide...
Page 139: ...EVO Installation Guide 139...
Page 140: ...140 EVO Installation Guide Printed in Canada 10 2007 paradox com...
Page 147: ...paradox com EVO192 EI04...