6.2.5 Generates a Utility Key Event on Open and Close
S
ECTIONS
[0601]
TO
[0632]: F
IRST
DIGIT
= 4
A Utility Key Event can be generated whenever the keyswitch input is opened or closed. The Utility Key Events
increase from 32 to 64 events; one event for each state.
When a keyswitch is defined with the Generate a Utility Key Event on Open and Close option, the Keyswitch
Partition Assignment and Keyswitch Options are disabled. To program a keyswitch to generate a Utility Key
Event:
1. Program the Activation Event of a PGM output with the
Utility Key
Event corresponding to the desired
keyswitch (see
PGM Programming Table
in the "EVO Programming Guide": Event Group 048).
2. Enable option
[4]
in the section corresponding to the desired keyswitch.
6.3 Keyswitch Partition Assignment
S
ECTIONS
[0601]
TO
[0632]: S
ECOND
DIGIT
= 1
TO
8
Each keyswitch must be assigned to one partition.
6.4 Keyswitch Options
Each keyswitch zone can be programmed with one or more options.
6.4.1 Disarm Only
Sections [0601] to [0632]: Option [3]
When enabled, the keyswitch can only disarm assigned partitions. The type of disarming is determined by the
other Keyswitch Options selected.
6.4.2 Stay/Instant Disarm Option (Keyswitch)
S
ECTIONS
[0601]
TO
[0632]: O
PTION
[4]
When enabled, the keyswitch can only disarm assigned Stay or Instant armed partitions. When option
[4]
is
disabled, the keyswitch can disarm partitions armed using any arming method.
6.4.3 Arm Only (Keyswitch)
S
ECTIONS
[0601]
TO
[0632]: O
PTION
[5]
When enabled, the keyswitch can only arm assigned partitions. The type of arming is determined by the other
Keyswitch Options selected.
6.4.4 Regular Arming (Keyswitch)
S
ECTIONS
[0601]
TO
[0632]: O
PTION
[6]
TO
[8]
With disabled, the arming option will be Regular arming.
6.4.5 Stay Arming (Keyswitch)
S
ECTIONS
[0601]
TO
[0632]: O
PTION
[6]
Activating the keyswitch will Stay Arm the partition.
6.4.6 Force Arming (Keyswitch)
S
ECTIONS
[0601]
TO
[0632]: O
PTION
[7]
Activating the keyswitch will force arm the selected partition.
6.4.7 Instant Arming (Keyswitch)
S
ECTIONS
[0601]
TO
[0632]: O
PTION
[8]
This option is identical to Stay arming except that all armed zones will become Instant Zones.
Summary of Contents for Digiplex EVO192
Page 1: ...Fire and Burglary Alarm System EVO192 Installation Guide...
Page 10: ...10 EVO Installation Guide...
Page 65: ...EVO Installation Guide 65 Event Reporting 10...
Page 125: ...EVO Installation Guide 125 Appendix F EVO192 CP 01 Implications as of June 13th 2014...
Page 136: ...136 EVO Installation Guide Notes...
Page 137: ...EVO Installation Guide 137...
Page 138: ...138 EVO Installation Guide...
Page 139: ...EVO Installation Guide 139...
Page 140: ...140 EVO Installation Guide Printed in Canada 10 2007 paradox com...
Page 147: ...paradox com EVO192 EI04...