Appendix D: Guidelines for Locating Smoke Detectors and CO Detectors
The following information is for general guidance only and it is recommended that local fire codes and
regulations be consulted when locating and installing smoke and CO alarms.
Smoke Detectors
Experiments with typical fires in homes indicate that detectable quantities of smoke precede detectable levels
of heat in most cases. For these reasons, smoke alarms should be installed outside of each sleeping area and on
each storey of the home.
The following information is for general guidance only and it is recommended that local fire codes and
regulations be consulted when locating and installing smoke alarms. It is recommended that additional smoke
alarms beyond those required for minimum protection be installed.
Additional areas that should be protected include: the basement; bedrooms, especially where smokers sleep;
dining rooms; furnace and utility rooms; and any hallways not protected by the required units. On smooth
ceilings, detectors may be spaced 9.1m (30 feet) apart as a guide. Other spacing may be required depending on
ceiling height, air movement, the presence of joists, un-insulated ceilings, etc.
Consult National Fire Alarm Code NFPA 72, CAN/ULC-S553-02 or other appropriate national standards for
installation recommendations. •
Warning:
Do not locate smoke detectors at the top of peaked or gabled ceilings; the dead air space in
these locations may prevent the unit from detecting smoke. • Avoid areas with turbulent air
flow, such as near doors, fans or windows. Rapid air movement around the detector may
prevent smoke from entering the unit. • Do not locate detectors in areas of high humidity. •
Do not locate detectors in areas where the temperature rises above 38
o
or below 5
o
C
Smoke detectors should always be installed in USA in accordance with Chapter 11 of NFPA 72, the National Fire
Alarm Code: 11.5.1.1.
Where required by applicable laws, codes, or standards for a specific type of occupancy, approved single- and
multiple-station smoke alarms shall be installed as follows:
1. In all sleeping rooms and guest rooms.
2. Outside of each separate dwelling unit sleeping area, within 6.4 m (21 ft) of any door to a sleeping room,
the distance measured along a path of travel.
3. On every level of a dwelling unit, including basements.
4. On every level of a residential board and care occupancy (small facility), including basements and
excluding crawl spaces and unfinished attics.
5. In the living area(s) of a guest suite.
6. In the living area(s) of a residential board and care occupancy (small facility).
CO detectors
Install one CO detector in each room that has a fuel burning appliance.
Make sure the alarm can be heard in the sleeping quarters of the building.
Summary of Contents for Digiplex EVO192
Page 1: ...Fire and Burglary Alarm System EVO192 Installation Guide...
Page 10: ...10 EVO Installation Guide...
Page 65: ...EVO Installation Guide 65 Event Reporting 10...
Page 125: ...EVO Installation Guide 125 Appendix F EVO192 CP 01 Implications as of June 13th 2014...
Page 136: ...136 EVO Installation Guide Notes...
Page 137: ...EVO Installation Guide 137...
Page 138: ...138 EVO Installation Guide...
Page 139: ...EVO Installation Guide 139...
Page 140: ...140 EVO Installation Guide Printed in Canada 10 2007 paradox com...
Page 147: ...paradox com EVO192 EI04...