background image

50

EVO Installation Guide

Note:

For ETL and UL The minimum permissible wire size to be employed shall be not smaller than No. 22 
AWG (0.32 mm2).

2. Use rubber bushings to protect the wires going through the metal housing.

3. Ground the metal box to a valid ground post or according to local electrical codes.

4.

Do not use any switch-controlled outlets to power the transformer. 

The system should be connected to 

the building’s power source (grounded outlet) with an AC/AC transformer.

5. Use a UL approved transformer. Use only LSS standard or a surge protected power supply. 

 

For residential installations use transformer made by Universal Power Group model: UB1640W 

6. The maximum charging current for the battery is 1amp. For UL installation 850ma charging current is 

required. 

7. Use only Metal boxes to comply with 

ANSI/NFPA 72

.

8. To prevent risk of electric shock, disconnect AC, battery, and phone cord BEFORE Servicing.

9. The knockouts in this box are compatible with standard conduit.

10. Main Supply Circuit – 110V, 60 Hz, with a transformer of max. power 40VA must be Listed to the LSS 

standard or must be Surge protected Power supply.

 

For residential installations use transformer made by Universal Power Group model: UB1640W 

11. The system should be installed in accordance with Chapter 2 of the National Fire Alarm Code, ANSI/NFPA 72

12. Installation of Residential Fire Warning Systems shall be in accordance with CAN/ULC-S540;

13. The panel will cease to process sensor trips if the voltage is under 8.5V.

14. Do no short the terminals of the transformer together. This causes the internal fuse to blow.

15. For the US and Canada: The transformer must be connected to a 110VAC/60Hz, 24-hour outlet which is not 

controlled by a switch other than an approved over-current protection device. Must be Listed to the LSS 
standard or must be Surge protected Power supply.

 

For residential installations use transformer made by Universal Power Group model: UB1640W 

16. For continued protection against risk of fire, replace fuses only with fuses of the same type and rating.

17. Install part TK278 Tamper kit in the panel metal box.

18. Wiring methods shall be in accordance with the National Electrical Code, ANSI/NFPA 70, the Standard for 

Installation and Classification of Burglar and Holdup Alarm Systems, UL 681, and the Standard for Central-
Station Alarm Services, UL 827.

19. Wiring methods in keeping with the requirements of CSA C22.1, Canadian Electrical Code, Part I, Safety 

Standard for Electrical Installations.

20. Connect a power on LED that shows when there is board power visible from outside of the box. The wires 

need to be connected to one of the AC terminals and the other to the COM terminal.

Summary of Contents for Digiplex EVO192

Page 1: ...Fire and Burglary Alarm System EVO192 Installation Guide...

Page 2: ...all warranty terms and conditions Please ensure that your use of the Paradox product is in compliance with local national and international laws 2014 Paradox Security Systems Ltd All rights reserved...

Page 3: ...stallation Procedure 13 2 4 Mounting the EVO192 Controller HUB2 ZX8 IP150 14 2 5 Mounting the K641 15 2 6 Mounting the TM50 15 2 7 Mounting the RTX3 15 2 8 Wiring 15 2 9 Earth Ground 17 2 10 AC Power...

Page 4: ...ATZ 33 4 4 Zone Definitions 33 4 5 Zone Partition Assignment 35 4 6 Zone Options 35 4 7 Input Speed 39 4 8 EOL on Hardwire Zones 39 4 9 Keypad Numbering 39 Chapter 5 Remote Control Programming 40 5 1...

Page 5: ...56 8 10 Timed Auto Arming 56 8 11 No Movement Auto Arming 56 8 12 Auto Arming Options 57 8 13 Switch To Stay Arming 57 8 14 Always Force Arm when Regular Arming 57 8 15 Auto Force on Stay Arming 58 8...

Page 6: ...13 Repeat Pager Report Code Transmission 76 10 14 Auto Test Report 76 10 15 Disarm Reporting Options 76 10 16 Zone Restore Report Options 76 10 17 Auto Report Code Programming 77 10 18 Closing Delinqu...

Page 7: ...Hardware Reset 87 14 2 Software Reset 87 14 3 Installer Code Lock 88 14 4 Daylight Savings Time 88 14 5 Daylight Savings Time Schedule 88 14 6 Battery Charge Current 89 14 7 Combus Speed 89 14 8 Tran...

Page 8: ...ng Keypad Zones 106 Programmable Output 106 Keypad Specific Instructions 106 K641R Access Control Connection 108 Programming 109 Message Programming K641 K641R 109 K641 Programming 110 Programmable Ou...

Page 9: ...ER MANUAL AND OR USER MANUAL 128 CHANGE THESE DEFAULTS IN THE PROGRAMMING GUIDE INSTALLER MANUAL 128 ADD THESE NOTES TO THE INSTALLER MANUAL 129 ADD THESE NOTES TO THE USER MANUAL 130 UNDOCUMENTED CHA...

Page 10: ...10 EVO Installation Guide...

Page 11: ...d indication of the information of the system such as events alerts warnings When required expand the number of zones in the EVO192 system by adding ZX8 and RTX3 expansion modules1 anywhere and in any...

Page 12: ...41 Keypad RTX3 Wireless Module 1 4 System Operation Once the EVO192 system is set up and programmed as described and explained in this manual the operation of the systems is done using the Keypads for...

Page 13: ...x and connect each one to 24 hour zones inputs on the EVO192 controller Pull all cables into the cabinet and prepare them for connection before mounting the circuit board into the back of the cabinet...

Page 14: ...washer screw the switch bracket to the wall you may need an anchor 5 Wire one of the switch wires to one of the on board zone inputs and the other to COM 6 Configure this zone to a 24h burglary zone...

Page 15: ...ounting the RTX3 For mounting instructions refer to the RTX3 manual RTX3 EI11 2 8 Wiring Location for the EVO192 board mounting pins There are 5 mounting pins Location for the Tamper switch Location f...

Page 16: ...ith the National Electrical Code ANSI NFPA 70 the Standard for Installation and Classification of Burglar and Holdup Alarm Systems UL 681 and the Standard for Central Station Alarm Services UL 827 Do...

Page 17: ...ead backup battery Verify the polarity as reversed connections will blow the battery fuse For details on how to set the Battery Charge Current to either 350mA or 850mA see see section 14 6 on page 89...

Page 18: ...ing 2 14 False Alarm Reduction In an effort to deter false alarms the EVO192 provides various programmable features including the following programmable features double knockout cross zoning auto zone...

Page 19: ..._ mA LED Keypads DGP2 648 _______ X 110mA __________ mA Motion Detector Modules DG85 DGP2 50 60 70 _______ X 30mA __________ mA Door Contact Modules DGP2 ZC1 _______ X 15mA __________ mA 1 Zone Expans...

Page 20: ...run of wire Available milliamps mA Length of each run of wire Available milliamps mA 30m 100ft 700 30m 100ft 700 30m 100ft 700 61m 200ft 700 61m 200ft 682 61m 200ft 429 91m 300ft 700 91m 300ft 454 91m...

Page 21: ...input terminal Power required by devices connected to control panel s Control Panel aux output 61m 15m APR PRT3 K641 7 5m 25ft 15m DGP2 70 7 5m APR ZX8 30m 100ft 22 AWG K641 15m K641 91m 300ft 290m D...

Page 22: ...nnections The control panel includes eight hardwired input terminals for use with traditional hardwired non combus door contacts smoke detectors and or motion detectors The control panel also supports...

Page 23: ...tacts No EOL N C With EOL Ul ULC Configuration CONTROL PANEL TERMINAL N O With EOL Ul ULC Configuration CONTROL PANEL TERMINAL N C Contacts No EOL With tamper recognition CONTROL PANEL TERMINAL N C Wi...

Page 24: ...igure 7 Double Zone Connections 2 21 Combus Connections The 4 wire combus can support 127 EVO48 or 254 EVO192 modules Use star and or daisy chain configuration The total length of wire cannot exceed 9...

Page 25: ...oring station if programmed UL Note Not to beusedwith UL Listed systems 2 22 2 ESL CleanMe Installation Connect ESL smoke detectors like the standard smoke detectors Avoid connecting more than 20 ESL...

Page 26: ...ving center phone number 999 999 999 Call waiting cancellation code 70 Phone number to program 70P999999999 Instructions that an automatic telephone dialer or similar device shall not be set or progra...

Page 27: ...nstaller must verify line seizure after every installation For TBR 21 compliance please note the following 1 The EVO can be connected to the telephone network via an RJ 11 connector 2 The Maximum Dial...

Page 28: ...remove the Memory Key Remove the write protect jumper Download to Control Panel 1 Insert the Memory Key onto the control panel s connector labelled MEM KEY 2 To download the contents of the Memory Key...

Page 29: ...pads The option is considered ON when the number appears within the brackets on the LCD keypad Turn options ON and OFF by pressing the corresponding keys on the keypad and then press ENTER to save For...

Page 30: ...the selected module To exit the Module Programming Mode press the CLEAR key on LCD keypads or the right action key Exit on Grafica keypads 1 Press and hold the 0 key 2 Key in the INSTALLER CODE defaul...

Page 31: ...Force Zone 5 6 Zone Alarm Type off off Steady Alarm off on Pulsed Alarm on off Silent Alarm on on Report Only 7 Intellizone 8 Delay before Transmission Ademco slow Silent Knight fast SESCOA Ademco ex...

Page 32: ...hardwired input terminal program the module s or control panel s serial number and the input number to the desired zone See the Digiplex Modules Programming Guide for details of its input numbers inp...

Page 33: ...same timers used for Stay Delay zones 4 4 3 Follow Zones section 0400 First digit 3 SECTIONS 0101 TO 0196 FIRST DIGIT 3 The control panel waits until the end of the Entry Delay before generating an al...

Page 34: ...e alarm as a Hold up Gas Heat Water or Freeze Alarm 4 4 8 24Hr Gas Zones SECTION 0400 FIRST DIGIT 8 SECTIONS 0101 TO 0196 FIRST DIGIT 8 When a 24Hr Gas zone opens the control panel will immediately ge...

Page 35: ...4 4 14 Stay Delay Zone SECTION 0400 FIRST DIGIT E AND F SECTIONS 0101 TO 0196 FIRST DIGIT E AND F Using the Regular or Force arming methods the control panel processes the zone as an Instant zone Usi...

Page 36: ...on a zone with option 7 enabled the control panel triggers the Intellizone Delay Fire Zones cannot be set as Intellizones An alarm will only be generated if the selected conditions occur during the In...

Page 37: ...32 seconds UL Note For UL Listed systems the detectionpattern of both zones must be installed so that each zone has the capability of protecting the area alone Partition 1 3110 Partition 3 3310 Parti...

Page 38: ...isabled The zone in alarm restores and reoccurs or an alarm occurs on another zone defined as Intellizone 3 Intellizone Zone Crossing default disabled An alarm occurs on another zone defined as Intell...

Page 39: ...30ms default 600ms 4 8 EOL on Hardwire Zones SECTION 3033 OPTION 7 default disabled If detection devices connected to hardwired input terminals use 1k end of line resistors enable option 7 in section...

Page 40: ...med into the EVO control panel and configured using a master code or installer code If the System Includes MG RTX3 Wireless Expansion Module But does not include K641 K641R keypad Remote controls must...

Page 41: ...Template 15 __ __ __ __ Button 1 Button 2 Button 3 Button 2 3 Disarm MG REM1 MG REM2 Default 1 B C 0 Regular Arm Utility Key 1 Utility Key 2 Disabled Disarm cannotbe modified 1B C0 00 00 Table 3 Temp...

Page 42: ...ONS 0601 TO 0632 FIRST DIGIT 2 To arm a partition using the Maintained Keyswitch turn the switch from the ON to the OFF position Disarm it by setting the key on the ON position 6 2 4 Generates a Utili...

Page 43: ...re options 6 4 1 Disarm Only Sections 0601 to 0632 Option 3 When enabled the keyswitch can only disarm assigned partitions The type of disarming is determined by the other Keyswitch Options selected 6...

Page 44: ...44 EVO Installation Guide Only one of the arming options Stay Force Instant and Regular can be selected...

Page 45: ...the WinLoad upload download software EVO also supports 32 virtual zones in addition to its security zones and access control doors Virtual zones can be used to automate PGM activations without occupy...

Page 46: ...des the control panel s bus into two completely isolated bus outputs two for each connected APR3 HUB2 It extends the combus communication bus by regenerating the signal between the control panel and i...

Page 47: ...ications anywhere in the world when your system detects activity So no matter where you are you will have access to arm disarm and more See Component Specifications and Installation guides at the end...

Page 48: ...A preventative maintenance agreement should be arranged through the local manufacturer s representative Though smoke detectors are designed for long life they may fail at any time Any smoke detector f...

Page 49: ...ator trouble beep Module and combus trouble beep All zone trouble beep See the EVO programming guide for instructions on enabling audible trouble notices through the keypad or through Babyware 7 3 6 R...

Page 50: ...installed in accordance with Chapter 2 of the National Fire Alarm Code ANSI NFPA 72 12 Installation of Residential Fire Warning Systems shall be in accordance with CAN ULC S540 13 The panel will ceas...

Page 51: ...Ground Floor Installation Up Den Living room Dining room Kitchen Toilet Utility room Entrance Control panel NVX80 NVX80 HD77 HD77 CO HD77 Smoke Ethernet Switch NV5 Door contact Window contacts Window...

Page 52: ...e line between the protected property and the communications service provider shall be for the exclusive use of the protected property and is not to be shared with other communications service provide...

Page 53: ...ing and Maintenance 7 5 1 Burglar Alarm Testing Two people are needed to complete this test One person will watch the screen on the keypad while the other person walks around the protected areas and o...

Page 54: ...d power supply For residential installations use transformer made by Universal Power Group model UB1640W 3 For US UL ETL Listed Class 2 wall building 120VAC 60Hz power supply with restraining means Fo...

Page 55: ...N 3034 OPTION 4 default disabled When enabled arming is restricted if a supervision loss signal from the Magellan Wireless System MG RTX3 is received 8 4 Restrict Arming on Tamper SECTION 3034 OPTION...

Page 56: ...ammed in section 3912 Enable option 1 in the desired section 8 10 1 Auto Arm Timer Enter the time when the partition should arm in the desired section 8 10 2 Postpone Auto Arming default 000 It is pos...

Page 57: ...ming If no Entry Delay zones are opened and closed during the Exit Delay after Regular arming a partition the control panel can switch from Regular arming to Stay arming Enable the option in the desir...

Page 58: ...ion the feature must be enabled in the corresponding partitions Select the section corresponding to the desired partition and enable or disable the desired options 8 18 Exit Delay default 060 The Exit...

Page 59: ...ogramming 000 into these sections will not lockout the keypad the control panel will transmit the Keypad Lockout report code programmed in section 3937 8 20 Bell Squawk The control panel can activate...

Page 60: ...e been bypassed while the system is armed 3 Auto Arming Emits 1 squawk every second for 60s before Auto Arming a partition Emits a series of 3 squawks every second for 10s before arming default disabl...

Page 61: ...m Enter the number of times from 001 to 255 000 no limit in one armed period that the control panel will re verify the zone status 9 2 3 Recycle Delay default 000 The Recycle Delay is the amount of ti...

Page 62: ...ION 3034 OPTIONS 5 AND 6 When the control panel detects a tamper or wire fault on a zone or on an expansion module the control panel can generate an alarm and or trouble as shown in the table below OF...

Page 63: ...control panel displays Zone Fault in the Trouble Display and transmits the defined report code see section 10 2 on page 67 ON OFF When disarmed Generates Trouble Only The control panel displays Zone...

Page 64: ...BELL output until a user cancels the alarm or when the Bell Cut Off Timer elapses Fire Alarm Same as audible operation except that the bell siren output will be pulsed UL Note For UL Listed systems a...

Page 65: ...EVO Installation Guide 65 Event Reporting 10...

Page 66: ...uto Report Code Programming ON PAGE 77 DIALING SEQUENCES FOR ARM DISARM REPORT CODES PARTITION 1 3127 PARTITION 5 3527 PARTITION 2 3227 PARTITION 6 3627 PARTITION 3 3327 PARTITION 7 3727 PARTITION 4 3...

Page 67: ...on page 77 10 2 1 Zone Alarm and Alarm Restore Report Codes SECTION 0400 FIRST AND SECOND BRACKETS SECTIONS 0201 TO 0296 FIRST AND SECOND BRACKETS The first set of 2 digits in the sections refer to t...

Page 68: ...d 3900 Cold Start control panel re starts after complete shutdown total power loss 3901 Warm Start control panel resets due to sudden problem other than power loss 3902 Test Report report generated au...

Page 69: ...56 3921 Quick Disarm partition disarms using One Touch Disarming feature see section 8 17 on page 58 3922 PC Disarm system disarmed using WinLoad or NEware software 3923 PC Disarm after Alarm system...

Page 70: ...equal to 1 1A 3944 Bell Output bell output is disconnected or the current is greater than or equal to 3A 3945 Clock Loss panel time lost see section 14 17 3946 Fire Loop Trouble tamper on a Fire Zone...

Page 71: ...ays when the partition should be armed or disarmed see Figure 20 Schedules are enabled when they are programmed Figure 20 Example of an Arming and a Disarming Report Schedule No Fail to Communicate fo...

Page 72: ...station telephone numbers Sections 3071 to 3074 represent monitoring station telephone numbers 1 through 4 Enter any digit up to a maximum of 32 Table 4 Special Telephone Number Keys Note The phone l...

Page 73: ...nated from When disabled the account number that is sent to the monitoring station corresponds to the partition where the event originated regardless of which MSTN is dialed 10 7 Reporting Formats SEC...

Page 74: ...g or any other value to use the default report code from the Automatic Report Code List in the EVO Programming Guide To program a set of default SIA FSK codes refer to Auto Report Code Programming on...

Page 75: ...6 the control panel will wait for the delay period programmed into section 3057 before uploading the report codes to the pager Enter any value between 001 and 127 to determine Pager Delay in seconds...

Page 76: ...Bell Cut Off Timer elapses see section 9 2 or when the alarm is disarmed When enabled the control panel sends the Zone Alarm Restore report codes see section 10 2 to the monitoring station as soon as...

Page 77: ...on is armed again EVO will transmit a Closing Delinquency report code to the monitoring station Enter a value from 001 to 255 days into the appropriate section Enter 000 to disable the Closing Delinqu...

Page 78: ...tion 3053 Entering a value between 000 and 016 will set the TLM Fail Timer to 32 seconds 11 2 Tone Pulse Dialing SECTION 3036 OPTION 4 default enabled 11 3 Pulse Ratio SECTION 3036 OPTION 5 default en...

Page 79: ...11 9 Call Waiting Cancel 1 Section 4 5 requires a programmable option for call waiting cancel shall be required on communicators that use media e g PSTN where call waiting may be provisioned The progr...

Page 80: ...hall be for the exclusive use of the protected property and is not to be shared with other communications service provider subscribers Note The phone line between the protected property and the commun...

Page 81: ...IALER connectors as shown in VDMP3 Installation Instructions 12 1 If using a 307USB or CONV4USB connect to the COM PORT connector as shown in VDMP3 Installation Instructions 12 1 Power up the EVO cont...

Page 82: ...Partition 5 1 to 8 3233 Partition 2 1 to 8 3633 Partition 6 1 to 8 3333 Partition 3 1 to 8 3733 Partition 7 1 to 8 3433 Partition 4 1 to 8 3833 Partition 8 1 to 8 4 Answering Machine Override If the...

Page 83: ...on Guide 83 9 Ring Counter Set the number of rings the VDMP3 will wait before the call is answered 3051 000 to 008 rings default 008 Note Changing these values will also affect PC communication via Wi...

Page 84: ...ate when another event occurs or after a period of time Enter the section that corresponds to the desired PGM and enable or disable option 1 default PGM Deactivation Event 13 3 Flexible PGM Deactivati...

Page 85: ...ed by the PGM Time Base Selection 13 5 1 PGM Time Base Selection The PGM Time Base Selection determines whether the PGM Timers are in minutes or seconds default seconds 13 6 PGM1 Becomes a 2 wire Smok...

Page 86: ...Installation Guide 13 8 PGM Initial Status Use this option to set the initial state for the PGM PGM 1 0919 Optio n Feature PGM 2 0929 4 ON Normally Closed PGM 3 0939 4 OFF Normally Open PGM 4 0949 PGM...

Page 87: ...o unlock software reset 4040 Resets the programmable sections from 0001 to 3991 to default even if Installer Code Lock is enabled except Event Buffer Panel ID PC Password PC Telephone Number and Zone...

Page 88: ...he Daylight Savings Time adjustment 4048 Entering this section resets the User Labels from the User Access Codes the Zone Labels from 0301 to 0396 Door Labels from 2301 to 2332 Partition Labels 3100 3...

Page 89: ...e connected to the serial port like WinLoad 14 9 Serial Port Baud Rate SECTION 3035 OPTION 8 Adjust depending on the baud rate set in WinLoad or NEware If communication between the control panel and t...

Page 90: ...low that corresponds to the function you wish to activate For Grafica keypads Press the center action key Options highlight the desired function and then press the center action key Ok STAY TEST REPOR...

Page 91: ...s sections 2301 to 2332 and the Partition Labels sections 3100 3200 3300 3400 3500 3600 3700 and 3800 to all the modules in the system that support these labels To transmit the labels in section 4004...

Page 92: ...counter that is reset at midnight 14 23 No AC Fail Display SECTION 3030 OPTION 6 default disabled When enabled the control panel will not display the AC Failure as a trouble When an AC Failure occurs...

Page 93: ...t the cursor s position DISARM Numeric or Alphanumeric Switches from numeric keys to alphanumeric keys and vice versa see Table 8 BYP Lower or Upper Case Switches the case setting from lower to upper...

Page 94: ...195 211 227 243 036 052 068 084 100 116 132 148 164 180 196 212 228 244 037 053 A069 085 101 117 133 149 165 181 197 213 229 245 038 054 070 086 102 118 134 150 166 182 198 214 230 246 039 055 071 08...

Page 95: ...196 212 228 244 037 053 069 085 101 117 165 181 197 213 229 245 038 054 070 086 102 118 166 182 198 214 230 246 039 055 071 087 103 119 167 183 199 215 231 247 040 056 072 088 104 120 168 184 200 216...

Page 96: ...01 117 133 149 165 181 197 213 229 245 022 038 054 070 086 102 118 134 150 166 182 198 214 230 246 023 039 055 071 087 103 119 135 151 167 183 199 215 231 247 024 040 056 072 088 104 120 136 152 168 1...

Page 97: ...56 The Installer Code can change the User Code Options Partition Assignment and Access Control Options but cannot change the personal identification number PIN Each digit in the System Master Code can...

Page 98: ...d System Manager s Manual or to the Grafica Graphic LCD Keypad Online Help 15 5 User Options SECTIONS 1002 TO 1999 USER OPTIONS SCREEN OPTIONS 1 TO 8 The User Options define how each user access code...

Page 99: ...ptions Feature Select Programming Enter Access Card User Options 1 2 Master Feature OFF OFFDisabled ON OFFMaster user can program user access codes only ON ONFull Master user can program user access c...

Page 100: ...or modify other user access codes ON OFF Master enabled User can create new user access codes with default options only can program PINs and User Labels ON ON Full Master enabled User can create and m...

Page 101: ...nded CE Closing Extend Cancel Alarm with PC Software 1 4A6 Cancel OR Disarm From Alarm Voice Disarm 1 4A7 Remote arm disarm OQ Remote Disarming Disarm with PC software 1 4A7 Remote arm disarm OQ Remot...

Page 102: ...ply trouble 1 3AA System trouble YP Power Supply Trouble Combus fault restore 3 333 Expansion module failure restore ER Expansion Restoral Module tamper restore 3 145 Expansion module tamper restore T...

Page 103: ...programming finished 1 628 Program mode Exit LS Local Program Success Module Fail to Communicate Restore 3 354 Fail to Communicate Restore YK Communication Restore System Event Default Contact ID Repo...

Page 104: ...3 4D 409 Keyswitch Open Close 82 136 Outdoor 19 327 Notification Appliance chk 4 4E REMOTE ACCESS 410 137 Tamper 1A SYSTEM PERIPHERAL TROUBLES 330 340 411 Callback Request Made 83 138 Near Alarm 1B 3...

Page 105: ...Group Bypass B9 623 Event Log 90 Full CE 466 Service On Off Premises A8 575 Swinger Bypass BA 624 Event Log Overflow CF SOUNDER RELAY DISABLES 520 576 Access Zone Shunt BB 625 Time Date Reset D0 520...

Page 106: ...ld be connected to the PGM Keypad Specific Instructions C 0 1 Memory Key Connection A memory key can be used to download programming to the K641 and K641R keypads C 0 2 Memory Key SECTIONS 510 AND 520...

Page 107: ...confirmation beep wait 5 seconds and remove the memory key after the second confirmation beep Set the memory key s jumper to OFF if you do not wish to accidentally overwrite its contents Figure 22 PMC...

Page 108: ...e Z2 K641R Combus To EVO control panel K641R K641R Fused external power supply recommended Door Lock IN4007 Diode K641R Paradoor 460 Request to Exit device Must be connected to Z2 terminal If a door c...

Page 109: ...and hold the 0 key 2 Enter INSTALLER CODE Default 000000 3 Enter section 4004 4 Enter the SERIAL of the source keypad The source is the programmed keypad whose data you want to copy to other keypads 5...

Page 110: ...Section 007 determines the amount of time without action before the keypad enters Confidential Mode The Confidential Mode Timer can be set from 005 seconds to 255 seconds Default 120 seconds C 0 13 T...

Page 111: ...default Option 1 ON Mute Option 2 OFF Exit Delay beep disabled Option 2 ON Exit Delay beep enabled default Option 4 OFF Chime on Zone Closure disabled default Option 4 ON Chime on Zone Closure enable...

Page 112: ...Deactivation Event SECTIONS 013 TO 016 If the PGM Deactivation Option is set to follow the PGM Deactivation event the PGM will return to its normal state when the event programmed in sections 013 to...

Page 113: ...ut action before the keypad enters Confidential Mode The Confidential Mode Timer can be set from 005 seconds to 255 seconds Default 120 secs C 0 33 Time Display Option SECTION 003 OPTION 8 Option 8 OF...

Page 114: ...002 OPTIONS 1 TO 8 The Access Control door can be assigned to one or more partition s in the alarm system This means that the actions performed with the Access Control Card will be directly linked to...

Page 115: ...ys C 0 47 Card Activates Door Unlocked Schedule SECTION 006 OPTION 1 Option 1 OFF The Schedule activates without Card Option 1 ON Card activates Door Unlocked Schedule default C 0 48 Door Left Open Ac...

Page 116: ...determine the number of seconds the Access Alarm will beep Default 5 seconds C 0 54 Door Forced Open Access Alarm SECTION 006 OPTION 3 When the Door Forced Open Alarm is disabled the following section...

Page 117: ...ectively Figure 27 Keypad Overview Figure 28 LED Partition Display Do not assign the same display number to more than one section For example you cannot assign value 002 to sections 003 and 004 The re...

Page 118: ...e preceding step unless entering in data in which case it will erase the current entry C 0 60 Section Reset Section 040 This section resets zone display sections 101 to 196 to default settings Enter 0...

Page 119: ...p enabled default C 0 66 Chime on Zone Closure Section 009 Option 5 Option 5 OFF Chime on Zone Closure disabled default Option 5 ON Chime on Zone Closure enabled C 0 67 Beep on Trouble Section 010 Opt...

Page 120: ...ter the sections that correspond to the EVENT GROUP FEATURE GROUP START and END of the PGM and enter the required data C 0 72 PGM Deactivation Mode SECTION 011 Option 2 Option 2 OFF Deactivation as pe...

Page 121: ...opriate national standards for installation recommendations Warning Do not locate smoke detectors at the top of peaked or gabled ceilings the dead air space in these locations may prevent the unit fro...

Page 122: ...122 EVO Installation Guide Figure 29 Recommendations for Smoke Detector Locations 4 min to 12 max 4 min to 12 max 4 min to 12 max 4 min to 12 max 4 min to 12 max Bedroom Bedroom Hallway...

Page 123: ...ay any member of the household can call from a neighbor s home or a cellular phone once safely outside If there are infants older adults or family members with mobility limitations make sure that some...

Page 124: ...y accessible location You don t want to have to search for it during a fire Always choose the escape route that is safest the one with the least amount of smoke and heat but be prepared to escape unde...

Page 125: ...EVO Installation Guide 125 Appendix F EVO192 CP 01 Implications as of June 13th 2014...

Page 126: ...nunciators enabled 4 2 2 3 Not programmable Exit time restart For re entry during exit delay Always Enabled Cannot be disabled 4 2 2 5 section 8 13 on page 57 Auto Stay Arm on non evacuated Premises I...

Page 127: ...l sounding device and an off premise transmission for SIA communication format K641 K641 TM50 Must be in the Installation guides 1 Add a note in the LCD manual near the mute programming statement Mute...

Page 128: ...i e two fire alarms anywhere on the system will cancel all pending fire delays and create immediate alarms 6 Call waiting cancel string a Program this before the telephone number 70P To enable the ca...

Page 129: ...standards iii To be CP 01 remote panic action shall be programmed on combined button only 17 Recent closing delay a If the option CP 01 is enabled section 3028 opt 3 the recent closing delay will alwa...

Page 130: ...CP 01 standards 24 There is a communicator delay of 30 seconds in this control panel It can be removed or it can be increased up to 45 seconds at the option of the end user by consulting with the Ins...

Page 131: ...ays Enabled Cannot be disabled 4 2 2 5 IM 10 1 Auto Stay Arm on Unvacated Premises If no exit after full arm Enabled Enabled 4 2 3 1 IM 7 1 1 to 7 1 4 Entry delay s 30 sec 255 sec 30 seconds At least...

Page 132: ...ine security Installations nor is it to be implemented on exit entry zones There is a communicator delay of 30 seconds in this control panel It can be removed or it can be increased up to 45 seconds a...

Page 133: ...15 WARNINGS INFORMATION TO USER This equipment has been tested and found to comply with the limits for Class B digital devices pursuant to Part 15 of FCC rules These limits are designed to provide re...

Page 134: ...a minimum of 15 minutes 30 minutes for Canada The Auto Test Report setting must be programmed to send a test transmission to the monitoring station at least once every 24 hours section 3037 options 3...

Page 135: ...ipment or equipment malfunctions may give the telecommunications company cause to request the user to disconnect the equipment Users should ensure for their own protection that the electrical ground c...

Page 136: ...136 EVO Installation Guide Notes...

Page 137: ...EVO Installation Guide 137...

Page 138: ...138 EVO Installation Guide...

Page 139: ...EVO Installation Guide 139...

Page 140: ...140 EVO Installation Guide Printed in Canada 10 2007 paradox com...

Page 141: ...e Tolerance Window 72 Assigning keyswitches to partitions 43 Audible Alarm 64 Bell Cut off Timer 61 Pulsed 36 Steady 36 Auto Force on Stay Arming 58 Auto Report Code Programming 77 Auto Test Report Pe...

Page 142: ...ections 21 Keyswitch Connections 18 Power 17 Single Zone Connections 22 Contact ID Pager 74 Contact ID Report Code List 104 D Daylight Savings Time 88 Daylight Savings Time Schedule 88 Delay Alarm Tra...

Page 143: ...ed 39 Installation Procedure 13 Installer Code 97 Installer Function Keys 90 Installer Lock 88 Installer Test Mode 90 Instant zone 34 Intellizone 36 Intellizone Delay 36 K Keypad Beep on Successful Ar...

Page 144: ...ry Key 28 Partition Labels 93 Partitioning 89 PGM PGM Activation Event 84 PGM Deactivation Event 85 PGM Deactivation Option 84 PGM Delay Timers 85 PGM Time Base Selection 85 PGM Initial Status 86 Poli...

Page 145: ...72 Serial Port Baud Rate 89 Serial Port Transmission of Zone Status 89 Sescoa 73 Shabbat Feature 90 SIA FSK 73 74 Silent Alarm 36 63 Silent Knight fast 73 Sirens 17 Special Arming Exit Delay 59 Specia...

Page 146: ...ons 61 Z Zone Labels 92 Zone Restore Report Options 76 Zone Status Transmission to Serial Port 89 Zones 24Hr Burglary zone 34 24Hr Buzzer 34 24Hr Freeze zone 34 24Hr Gas zone 34 24Hr Heat zone 34 24Hr...

Page 147: ...paradox com EVO192 EI04...

Reviews: