EVO Installation Guide
55
Arming and Disarming Options
8
8.1 Arming Follows Partition
(default =
disabled
) A partition can be set to follow the arming and disarming status of one or more partitions.
8.2 Trouble Latch
S
ECTION
[3033]: O
PTION
[6]
With the Trouble Latch feature disabled, when a trouble occurs and is corrected, the trouble is automatically
cleared and no longer displayed. With the Trouble Latch feature enabled, the trouble will remain displayed until
it is manually cleared by the user. To clear the trouble, the user must enter the trouble display and then exit the
trouble display. For LCD and LED keypads, press
[
CLEAR
]
to exit. For Grafica keypads, press the left action key
(
Back
) to exit.
Only troubles that have been corrected can be cleared. If a trouble has not been corrected, it will
continue to be displayed even if the user tries to clear the trouble by using the method described
above.
8.3 Restrict Arming on Supervision Loss
S
ECTION
[3034]: O
PTION
[4]
(default =
disabled
) When enabled, arming is restricted if a supervision loss signal from the Magellan Wireless
System MG-RTX3 is received.
8.4 Restrict Arming on Tamper
S
ECTION
[3034]: O
PTION
[8]
(default =
disabled
) When enabled, the control panel prevents arming if it detects a tamper on a zone or
module (see
section 9.5
on page 62). Partitions will not arm until the Installer Code is entered and the tamper
trouble conditions are corrected.
8.5 Restrict Arming on AC Failure
S
ECTION
[3035]: O
PTION
[1]
(default =
disabled
) When enabled, the control panel prevent arming if it detects a loss of AC power.
8.6 Restrict Arming on Battery Failure
S
ECTION
[3035]: O
PTION
[2]
(default =
disabled
) When enabled, the control panel prevents arming if it detects a battery loss or if the
battery voltage is less than 10.5V.
Section:
Partition 1: [3121]
Partition 2: [3221]
Partition 3: [3321]
Partition 4: [3421]
Partition 5: [3521]
Partition 6: [3621]
Partition 7: [3721]
Partition 8: [3821]
Partition arms & disarms with:
Option [1] =
Partition 1
Option [2] =
Partition 2
Option [3] =
Partition 3
Option [4] =
Partition 4
Option [5] =
Partition 5
Option [6] =
Partition 6
Option [7] =
Partition 7
Option [8] =
Partition 8
Summary of Contents for Digiplex EVO192
Page 1: ...Fire and Burglary Alarm System EVO192 Installation Guide...
Page 10: ...10 EVO Installation Guide...
Page 65: ...EVO Installation Guide 65 Event Reporting 10...
Page 125: ...EVO Installation Guide 125 Appendix F EVO192 CP 01 Implications as of June 13th 2014...