15-72
Error
code
Name
Opera-
tion
status
Description and steps to take
FP
-e
FP
0
FP
0R
FP
Σ
FP
-X
FP
2
FP2
SH
FP
10S
H
E29
Configu-
ration
parameter
error
Stops
A parameter error was detected in the
MEWNET-W2 configuration area. Set a
correct parameter.
A A
E30 Interrupt
error 0
Stops
Probably a hardware abnormality.
⇒
Please contact your dealer.
E31 Interrupt
error 1
Stops
An interrupt occurred without an interrupt
request . A hardware problem or error due to
noise is possible.
⇒
Turn off the power and check the noise
conditions.
A A A A A A A A
E32 Interrupt
error 2
Stops
There is no interrupt program for an interrupt
which occurred.
⇒
Check the number of the interrupt program
and change it to agree with the interrupt
request..
A A A A A A A A
E33
Multi-CPU
data
unmatch
error
CPU2
Stops
This error occurs when a FP3/FP10SH is
used as CPU2 for a multi-CPU system.
⇒
Refer to “Multi-CPU system Manual”.
A A
E34 I/O status
error
Stops
An abnormal unit is installed.
-FP
Σ
, FP0R(FP0R mode),FP-X, FP2,FP2SH
and FP10SH:
Check the contents of special data register
DT90036 and locate the abnormal unit. Then
turn off the power and replace the unit with a
new one.
-FP3:
Check the contents of special data register
DT9036 and locate the abnormal unit. Then
turn off the power and replace the unit with a
new one.
A A A
A A
E35
MEWNET-F
slave
illegal unit
error
Stops
A unit, which cannot be installed on the slave
station of the MEWNET-F link system, is
installed on the slave station.
⇒
Remove the illegal unit from the slave
station.
A A A
E36
MEWNET-F
(remote
I/O)
limitation
error
Stops
The number of slots or I/O points used for
MEWNET-F(remote I/O) system exceeds the
limitation.
⇒
Re-configure the system so that the
number of slots and I/O points is within the
specified range.
A A A
E37
MEWNET-F
I/O
mapping
error
Stops
I/O overlap or I/O setting that is over the
range is detected in the allocated I/O and
MEWNET-F I/O map.
⇒
Re-configure the I/O map correctly
A A A
A: Available
Summary of Contents for FP0R Series
Page 1: ......
Page 6: ...iv ...
Page 14: ...xii ...
Page 15: ...Chapter 1 Functions and Restrictions of the Unit ...
Page 24: ...1 10 ...
Page 25: ...Chapter 2 Specifications and Functions of Control Unit ...
Page 38: ...2 14 ...
Page 39: ...Chapter 3 Expansion ...
Page 45: ...3 7 3 4 Terminal layout diagram Model No Terminal layout diagrams E8RS E8RM E16RS E16RM E8YRS ...
Page 48: ...3 10 ...
Page 49: ...Chapter 4 I O Allocation ...
Page 53: ...Chapter 5 Installation and Wiring ...
Page 73: ...Chapter 6 Preparation of USB Port ...
Page 77: ...6 5 5 Click Finish on the following screen to be displayed ...
Page 79: ...6 7 4 Double click on FP0R 5 Click Update Driver ...
Page 84: ...6 12 ...
Page 85: ...Chapter 7 Communication ...
Page 139: ...7 55 Sample program For Type II Use a program as below to directly specify a MODBUS address ...
Page 141: ...Chapter 8 High speed Counter Pulse Output and PWM Output Functions ...
Page 142: ...8 2 ...
Page 199: ...Chapter 9 Security Functions ...
Page 211: ...Chapter 10 Other Functions ...
Page 217: ...Chapter 11 Self Diagnostic and Troubleshooting ...
Page 227: ...Chapter 12 Precautions During Programming ...
Page 242: ...12 16 ...
Page 243: ...Chapter 13 Specifications ...
Page 254: ...13 12 ...
Page 255: ...Chapter 14 Dimensions and Others ...
Page 262: ...14 8 ...
Page 263: ...Chapter 15 Appendix ...
Page 344: ...15 82 15 7 ASCII Codes ...
Page 346: ......
Page 347: ......
Page 348: ......