8-43
8.4.13 JOG Positioning Control Instruction (F171)
-
When the trigger (execution condition) turns on, the JOG operation is started. When the position control
start input becomes effective, a specified pulse is output and the deceleration stop is performed.
-
The position control start input becomes effective when the leading edge of the external inputs X0 to X3
or the bit 6 of the special data register DT90052 is detected. To use the external inputs X0 to X3,
specify them by the system register No. 402 for each channel.
Control method of JOG positioning control instruction (F171): Type 0 and Type 1
Type 0
-
Once the trigger (execution condition) turns on, the JOG operation is started, and acceleration is
performed up to the target speed.
-
When the position control start input becomes effective, pulses are output up to a specified target value.
-
The speed can be changed by rewriting the target speed during the operation after executing the
instruction.
Type 1
-
Once the trigger (execution condition) turns on, the JOG operation is started, and acceleration is
performed up to the target speed 1.
-
When the position control start input becomes effective, the speed is changed to the target speed 2 at a
specified changeover time and pulses are output up to a specified target value.
-
The speed cannot be changed after executing the instruction.
When Target speed 1 > Target speed 2
When Target speed 1 < Target speed 2
Summary of Contents for FP0R Series
Page 1: ......
Page 6: ...iv ...
Page 14: ...xii ...
Page 15: ...Chapter 1 Functions and Restrictions of the Unit ...
Page 24: ...1 10 ...
Page 25: ...Chapter 2 Specifications and Functions of Control Unit ...
Page 38: ...2 14 ...
Page 39: ...Chapter 3 Expansion ...
Page 45: ...3 7 3 4 Terminal layout diagram Model No Terminal layout diagrams E8RS E8RM E16RS E16RM E8YRS ...
Page 48: ...3 10 ...
Page 49: ...Chapter 4 I O Allocation ...
Page 53: ...Chapter 5 Installation and Wiring ...
Page 73: ...Chapter 6 Preparation of USB Port ...
Page 77: ...6 5 5 Click Finish on the following screen to be displayed ...
Page 79: ...6 7 4 Double click on FP0R 5 Click Update Driver ...
Page 84: ...6 12 ...
Page 85: ...Chapter 7 Communication ...
Page 139: ...7 55 Sample program For Type II Use a program as below to directly specify a MODBUS address ...
Page 141: ...Chapter 8 High speed Counter Pulse Output and PWM Output Functions ...
Page 142: ...8 2 ...
Page 199: ...Chapter 9 Security Functions ...
Page 211: ...Chapter 10 Other Functions ...
Page 217: ...Chapter 11 Self Diagnostic and Troubleshooting ...
Page 227: ...Chapter 12 Precautions During Programming ...
Page 242: ...12 16 ...
Page 243: ...Chapter 13 Specifications ...
Page 254: ...13 12 ...
Page 255: ...Chapter 14 Dimensions and Others ...
Page 262: ...14 8 ...
Page 263: ...Chapter 15 Appendix ...
Page 344: ...15 82 15 7 ASCII Codes ...
Page 346: ......
Page 347: ......
Page 348: ......