13-9
13.2.2 I/O Numbers for FP0 Expansion Unit
•
I/O numbers do not need to be set as I/O allocation is performed automatically by the PLC when an
expansion I/O unit is added.
•
The I/O allocation for expansion units is determined by the installation location.
Unit type
Allocation points
Expansion
unit 1
Expansion
unit 2
Expansion
unit 3
FP0/FP0R
expansion unit
E8X
Input: 8 points
X20 to X27
X40 to X47
X60 to X67
E8R
Input: 4 points
X20 to X23
X40 to X43
X60 to X63
Output: 4 points
Y20 to Y23
Y40 to Y43
Y60 to Y63
E8YT/P
E8YR
Output: 8 points
Y20 to Y27
Y40 to Y47
Y60 to Y67
E16X
Input: 16 points
X20 to X2F
X40 to X4F
X60 to X6F
E16R
E16T/P
Input: 8 points
X20 to X27
X40 to X47
X60 to X67
Output: 8 points
Y20 to Y27
Y40 to Y47
Y60 to Y67
E16YT/P
Output: 16 points
Y20 to Y2F
Y40 to Y4F
Y60 to Y6F
E32T/P
Input: 16 points
X20 to X2F
X40 to X4F
X60 to X6F
Output: 16 points
Y20 to Y2F
Y40 to Y4F
Y60 to Y6F
FP0 analog I/O
unit
FP0-A21
Input: 16 points
(ch0)
WX2
(X20 to X2F)
WX4
(X40 to X4F)
WX6
(X60 to X6F)
Input: 16 points
(ch1)
WX3
(X30 to X3F)
WX5
(X50 to X5F)
WX7
(X70 to X7F)
Output: 16 points
WY2
(Y20 to Y2F)
WY4
(Y40 to Y4F)
WY6
(Y60 to Y6F)
FP0 A/D
converter unit
FP0
thermocouple
unit
FP0-A80
FP0-TC4
FP0-TC8
Input: 16 points
(ch0, 2, 4, 6)
WX2
(X20 to X2F)
WX4
(X40 to X4F)
WX6
(X60 to X6F)
Input: 16 points
(ch1, 3, 5, 7)
WX3
(X30 to X3F)
WX5
(X50 to X5F)
WX7
(X70 to X7F)
FP0
RTD unit
FP0-RTD
Input (16 points)
CH0, 2, 4
WX2
(X20 to X2F)
WX4
(X40 to X4F)
WX6
(X60 to X6F)
Input (16 points)
CH1, 3, 5
WX3
(X30 to X3F)
WX5
(X50 to X5F)
WX7
(X70 to X7F)
Output (16 points)
WY2
(Y20 to Y2F)
WY4
(Y40 to Y4F)
WY6
(Y60 to Y6F)
FP0 D/A
converter unit
FP0-A04V
FP0-A04I
Input: 16 points
WX2
(X20 to X2F)
WX4
(X40 to X4F)
WX6
(X60 to X6F)
Output: 16 points
(ch0, 2)
WY2
(Y20 to Y2F)
WY4
(Y40 to Y4F)
WY6
(Y60 to Y6F)
Output: 16 points
(ch1, 3)
WY3
(Y30 to Y3F)
WY5
(Y50 to Y5F)
WY7
(Y70 to Y7F)
FP0 I/O link
unit
FP0-IOL
Input: 32 points
X20 to X3F
X40 to X5F
X60 to X7F
Output: 32 points
Y20 to Y3F
Y40 to Y5F
Y60 to Y7F
•
The data of each channel for FP0 A/D converter unit (FP0-A80), FP0 thermocouple unit (FP0-
TC4/FP0-TC8), FP0 D/A converter unit (FP0-A04V/P0-A04I) is switched and read/write using a
program that includes the flag for switching converted data.
•
Regarding FP0 CC-Link slave unit, please refer to the exclusive manual.
Summary of Contents for FP0R Series
Page 1: ......
Page 6: ...iv ...
Page 14: ...xii ...
Page 15: ...Chapter 1 Functions and Restrictions of the Unit ...
Page 24: ...1 10 ...
Page 25: ...Chapter 2 Specifications and Functions of Control Unit ...
Page 38: ...2 14 ...
Page 39: ...Chapter 3 Expansion ...
Page 45: ...3 7 3 4 Terminal layout diagram Model No Terminal layout diagrams E8RS E8RM E16RS E16RM E8YRS ...
Page 48: ...3 10 ...
Page 49: ...Chapter 4 I O Allocation ...
Page 53: ...Chapter 5 Installation and Wiring ...
Page 73: ...Chapter 6 Preparation of USB Port ...
Page 77: ...6 5 5 Click Finish on the following screen to be displayed ...
Page 79: ...6 7 4 Double click on FP0R 5 Click Update Driver ...
Page 84: ...6 12 ...
Page 85: ...Chapter 7 Communication ...
Page 139: ...7 55 Sample program For Type II Use a program as below to directly specify a MODBUS address ...
Page 141: ...Chapter 8 High speed Counter Pulse Output and PWM Output Functions ...
Page 142: ...8 2 ...
Page 199: ...Chapter 9 Security Functions ...
Page 211: ...Chapter 10 Other Functions ...
Page 217: ...Chapter 11 Self Diagnostic and Troubleshooting ...
Page 227: ...Chapter 12 Precautions During Programming ...
Page 242: ...12 16 ...
Page 243: ...Chapter 13 Specifications ...
Page 254: ...13 12 ...
Page 255: ...Chapter 14 Dimensions and Others ...
Page 262: ...14 8 ...
Page 263: ...Chapter 15 Appendix ...
Page 344: ...15 82 15 7 ASCII Codes ...
Page 346: ......
Page 347: ......
Page 348: ......