15-65
Num-
ber
Name
Boolean
Ope-
rand
Description
Ste
ps
FP
0/
FP
-e
FP0
R
FP
Σ
FP
-X
FP2
FP
2SH
/F
P1
0SH
F347
P347
Floating-point
type data
upper and
lower limit
control
FLIMT
PFLIMT
S1, S2,
S3, D
When (S1+1, S1)>(S3+1, S3),
(S1+1, S1)
→
(D+1, D)
When (S2+1, S2)<(S3+1, S3),
(S2+1, S2)
→
(D+1, D)
When (S1+1, S1)<or = (S3+1,
S3)<or =(S2+1, S2), (S3+1,
S3)
→
(D+1, D)
17
F348
P348
Floating-point
type data
dead-band
control
FBAND
PFBAND
S1, S2,
S3, D
When (S1+1, S1)>(S3+1, S3),
(S3+1, S3)
−
(S1+1, S1)
→
(D+1, D)
When (S2+1, S2)<(S3+1, S3),
(S3+1, S3)
−
(S2+1, S2)
→
(D+1, D)
When (S1+1, S1)<or = (S3+1,
S3)<or =(S2+1, S2), 0.0
→
(D+1, D)
17
F349
P349
Floating-point
type data
zone control
FZONE
PFZONE
S1, S2,
S3, D
When (S3+1, S3)<0.0,
(S3+1, S3)+(S1+1, S1)
→
(D+1, D)
When (S3+1, S3)=0.0, 0.0
→
(D+1,
D)
When (S3+1, S3)>0.0, (S3+1,
S3)+(S2+1, S2)
→
(D+1, D)
17
F350
P350
Floating-point
type data
maxi-mum
value
FMAX
PFMAX
S1, S2,
D
Searches the maximum value in the
real number data table between the
area selected with “S1” and “S2”,
and stores it in the (D+1, D). The
address relative to “S1” is stored in
(D+2).
8
F351
P351
Floating-point
type data
mini-mum
value
FMIN
PFMIN
S1, S2,
D
Searches the minimum value in the
real number data table between the
area selected with “S1” and “S2”,
and stores it in the (D+1, D). The
address relative to “S1” is stored in
(D+2).
8
F352
P352
Floating-point
type data total
and mean
values
FMEAN
PFMEAN
S1, S2,
D
The total value and the mean value
of the real number data from the
area selected with “S1” to “S2” are
obtained. The total value is stored in
the (D+1, D) and the mean value is
stored in the (D+3, D+2).
8
F353
P353
Floating-point
type data sort
FSORT
PFSORT
S1, S2,
S3
The real number data from the area
specified by “S1” to “S2” are stored
in ascending order (the smallest
word is first) or descending order
(the largest word is first).
8
F354
P354
Scaling of
real number
data
FSCAL
PFSCAL
S1, S2,
D
Scaling (linearization) on a real
number data table is performed, and
the output (Y) to an input value (X)
is calculated.
12
*1 *2 *3 *3
: Available, : Not available, : Not available partially
*1) This instruction is available for FP
Σ
32k type.
*2) This instruction is available for FP-X Ver. 1.13 or later.
*3) This instruction is available for FP2/FP2SH Ver. 1.5 or later. FP10SH cannot be used.
Summary of Contents for FP0R Series
Page 1: ......
Page 6: ...iv ...
Page 14: ...xii ...
Page 15: ...Chapter 1 Functions and Restrictions of the Unit ...
Page 24: ...1 10 ...
Page 25: ...Chapter 2 Specifications and Functions of Control Unit ...
Page 38: ...2 14 ...
Page 39: ...Chapter 3 Expansion ...
Page 45: ...3 7 3 4 Terminal layout diagram Model No Terminal layout diagrams E8RS E8RM E16RS E16RM E8YRS ...
Page 48: ...3 10 ...
Page 49: ...Chapter 4 I O Allocation ...
Page 53: ...Chapter 5 Installation and Wiring ...
Page 73: ...Chapter 6 Preparation of USB Port ...
Page 77: ...6 5 5 Click Finish on the following screen to be displayed ...
Page 79: ...6 7 4 Double click on FP0R 5 Click Update Driver ...
Page 84: ...6 12 ...
Page 85: ...Chapter 7 Communication ...
Page 139: ...7 55 Sample program For Type II Use a program as below to directly specify a MODBUS address ...
Page 141: ...Chapter 8 High speed Counter Pulse Output and PWM Output Functions ...
Page 142: ...8 2 ...
Page 199: ...Chapter 9 Security Functions ...
Page 211: ...Chapter 10 Other Functions ...
Page 217: ...Chapter 11 Self Diagnostic and Troubleshooting ...
Page 227: ...Chapter 12 Precautions During Programming ...
Page 242: ...12 16 ...
Page 243: ...Chapter 13 Specifications ...
Page 254: ...13 12 ...
Page 255: ...Chapter 14 Dimensions and Others ...
Page 262: ...14 8 ...
Page 263: ...Chapter 15 Appendix ...
Page 344: ...15 82 15 7 ASCII Codes ...
Page 346: ......
Page 347: ......
Page 348: ......