High
−
level Instructions
3
−
659
Outline
This instruction carries out upper and lower limit control for 32-bit data.
For the FP0R/FP
Σ
/FP
−
X, the P type high
−
level instruction “P286
(PDLIMT)” is not available.
Program example
Ladder Diagram
Boolean
Ladder Diagram
Address
Instruction
S1
Trigger
S3
S2
D
F286 DLIMT, DT10, DT20, DT30, DT40
10
R0
10
11
ST
R
0
F286
(DLIMT)
DT
10
DT
20
DT
30
DT
40
S1
The area where the lower limit is stored or the lower limit data. (2 words)
S2
The area where the upper limit is stored or the upper limit data. (2 words)
S3
The area where the input value is stored or the input value data. (2 words)
D
The area where the output value is stored. (2 words)
Operands
Operand
Relay
Timer/Counter
Register
Index
register
Constant
Index
modifier
Integer
device
Operand
WX WY WR WL
SV
EV
DT LD
FL
I
K
H
f
modifier device
S1
A
A
A
A
A
A
A
A
A
A
A
A
N/A
A
N/A
S2
A
A
A
A
A
A
A
A
A
A
A
A
N/A
A
N/A
S3
A
A
A
A
A
A
A
A
A
A
A
A
N/A
A
N/A
D
N/A
A
A
A
A
A
A
A
A
A
N/A N/A N/A
A
N/A
F286
P286
(PDLIMT)
(DLIMT)
32-bit data upper and lower limit control
A: Available
N/A: Not Available
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for FP-E
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 24: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 1333: ...5 245 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...