High
−
level Instructions
3
−
773
2
−
1: Auto
−
tuning bias value (S4+6)
Auto
−
tuning is executed with (set value (SP)
−
auto
−
tuning bias value) as a set value (SP’).
It is used to control excessive temperature rise while auto
−
tuning is performed.
For the forward operaiton, auto
−
tuning is executed with (set value (SP) + this set value) as a set value.
Temperature
During auto
−
tuning
KP, TI and TD calculation
PID control
Auto
−
tuning in reverse operation
Time
Set value
(SP)
Auto
−
tuning bias value
(SP’)
Auto
−
tuning in forward operation
Temperature
KP, TI and TD calculation
PID control
Time
Set value
(SP)
Auto
−
tuning bias value
(SP’)
During auto
−
tuning
Note) Even if starting auto
−
tuning in the condition that measured value (PV) is close to set value (SP),
auto
−
tuning is peformed with the above SP’.