High
−
level Instructions
3 - 6
Example 2: The execution condition (trigger) is programmed once using the
PSHS, RDS and POPS instructions.
F0 MV, WR 0 , DT 10
F0 MV, LD 1 , DT 11
P115 PFIFT, DT 10 , DT 11
X0
PSHS
RDS
POPS
3.1.4
“F” and “P” Type High-level Instructions
For more high
−
level instructions, “F” and “P” types are available.
“F” type high-level instruction
While the execution condition (trigger) is on, the instruction is executed at each scan
repeatedly.
F
−
type high-level
instruction
Execution condition
(Trigger)
1 scan
on
off
Execution
“P” type high-level instruction
The leading edge of the execution condition (trigger) is detected, and a single scan is
executed.
P
−
type high-level
instruction
Execution condition
(Trigger)
1 scan
on
off
Execution
As long as the execution condition (trigger) for the “P” type instruction continues to be
on, the instruction is executed only at the rise of the condition, and is not subsequently
executed.
If the mode is switched to the RUN mode, or the power supply is turned on in the RUN
mode, the instruction is not executed in the first scan if the execution condition (trigger)
for the “P” type instruction has been in effect from the beginning.
Operation
of instruc-
tion
RUN
(Power: on)
Executed
Not exe-
cuted
Execution
condition
(Trigger)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for FP-E
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 24: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 1333: ...5 245 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...