High
−
level Instructions
3
−
399
Explanation of example
Five words of data stored in data registers DT10 to DT14 of CPU are written into the addresses starting from
K0 to K4 of the intelligent unit shared memory (located in slot 0) when trigger R10 turns on.
0
1
2
3
4
DT0
DT1
0
2
1
3
4
5
6
DT10
DT11
DT12
DT14
DT13
(Slot No.)
CPU
Intelligent unit
Power
CPU
5 words
Description
Writes n words of the initial data from the area specified by S2 of the CPU to the address specified by D of the
shared memory of the intelligent unit specified by S1.
Specifying the various items
Specifying the slot number and bank number (S1)
Specify the slot in which the intelligent unit has been installed. If the memory has a bank, enter a specification
that matches the bank number.
Number of words to be written (n)
Specify this using a K constant.
To write 10 words of data, specify “K10”.
Initial address written to the shared memory of the intelligent unit (D)
Specify this referring to the table of shared memories for the various intelligent units.
To specify address 2, specify “K2”.
Flag conditions
・
Error flag (R9007): Turns on and stays on when:
・
Error flag (R9008): Turns on for an instant when:
−
The value of S1 exceeds the limit of specified range.
−
The area specified using the index modifier exceeds the limit.
−
The range of writing data exceeds the area specified using S2.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for FP-E
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 24: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 1333: ...5 245 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...