High
−
level Instructions
3
−
561
Outline
Measures the number of pulses and the pulse period of the specified
high
−
speed counter channel when using the high
−
speed counter
function.
Program example
Ladder Diagram
Boolean
Ladder Diagram
Address
Instruction
10
F178 PLSM , DT100 , DT101 , DT200
S1
R3
DF
D
S2
10
11
ST
R
3
F178
(PLSM)
DT
100
DT
101
DT
200
S1
Specification of channel No. and No. of moving average.
S2
Counting period
D
Starting address of the destination area
Operands
Operand
Relay
Timer/Counter
Register
Index
register
SWR SDT
Constant
Index
modifier
Operand
WX WY WR WR
SV
EV
DT
LD
In (*1)
SWR SDT
K
H
modifier
S1
A
A
A
A
A
A
A
A
A
N/A
N/A
A
A
A
S2
A
A
A
A
A
A
A
A
A
N/A
N/A
A
A
A
D
N/A
A
A
A
A
A
A
A
A
N/A
N/A
N/A N/A
A
(
*
1) I0 to ID
Description
The number of pulses or the pulse period of the specified high
−
speed counter channel is measured based on
the control data specified by [S1].
In the measurement of the number of pulses, the number of pulses of the specified high
−
speed counter
counted during the period specified by S2 is counted.
The average of the number of moving average is calculated with the specified period and stored in D and
D+1.
When the number of average is n,
−
1 is output during the (n*counting period) time after the execution of the
instruction.
In the pulse period measurement in 1us unit, a period of 1 pulse right after the execution of this instruction is
counted and stored in D+2 and D+3.
In the pulse period measurement in 1ms unit, the measured value is stored in D+4 and D+5 every time the
measurement of a period of 1 pulse completes.
The same channel cannot be specified at the same time with other high
−
speed counter control instructions
<F165(CAM0), F166(HC1S), F167(HC1R)>.
An exclusive control is implemented by the high
−
speed counter control flags (R9110 to R9115).
The number of channels that the instruction can be executed simultaneously is two.
The trigger should be always ON while the pulse is being measured with this instruction.
Turning OFF the trigger stops the measurement.
FP0R
Input pulse measurement
5
F178
(PLSM)
Availability
FP0R
A: Available
N/A: Not Available
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for FP-E
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 24: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 1333: ...5 245 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...