High
−
level Instructions
3
−
15
Explanation of example
The contents of data registers DT12 and DT11 are inverted and transferred to data registers DT21 and DT20
when trigger R0 turns on.
Invert and
transfer
DT10
DT11
DT12
DT20
DT21
DT22
H 34A
H
0
H 25AC
H FFFD
[S]
H 1111
H FFFF
[D]
H
2
H
0
H 25AC
H FFFD
DT10
DT11
DT12
[S]
H FFFF
H FFFF
DT20
DT21
DT22
[D]
R0: on
“
F3 (DMV/)
” execution
Description
The 32-bit data or 32-bit equivalent constant specified by S is inverted and transferred to the 32-bit area
specified by D.
1 1 0 0 1 1 0 1 0 0 0 1 0 1 0 1
S
S+1
0 0 1 1 0 0 1 0 1 1 1 0 1 0 1 0
D
D+1
0 0 0 0 0 1 1 1 0 1 0 1 1 0 1 1
1 1 1 1 1 0 0 0 1 0 1 0 0 1 0 0
When processing 32-bit data, the higher 16-bit areas (S+1, D+1) are automatically determined once the
lower 16-bit areas (S, D) are specified.
Flag conditions
・
Error flag (R9007): Turns on and stays on when the area specified using the index modifier
exceeds the limit.
・
Error flag (R9008): Turns on for an instant when the area specified using the index modifier
exceeds the limit.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for FP-E
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 24: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 1333: ...5 245 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...