17-13
17.4.2 Setting Parameter Control Area
This is the area to write the setting values of the positioning parameters and positioning data in the
shared memory into FROM(Flash memory), or to execute the recalculation of the positioning data.
The number of writing to FROM in the positioning unit is announced to the CPU through this area, and
writing the positioning parameters and positioning data in the shared memory to FROM is requested.
Also, the recalculation starting table number is set to recalculate the positioning data in the standard
area.
Bank
Offset
address
Name
Descriptions
Default
value
Setting
range
Unit
00H
080H
Annunciation of
number of
writing to FROM
Announces the number of writing the
positioning parameters and data in the
shared memory into FROM.
0
-
times
081H
Request for
writing to FROM
When writing into FROM by Configurator
PM, the following procedures will be
automatically performed.
When writing into FROM by ladder
programs, it is necessary to achieve the
following Configurator PM operation by
the ladder programs.
1. Write 5555H in this area by the ladder
program.
2. The positioning unit checks 5555H,
and write 6666H over in the same
area.
3. Check 6666H by the ladder program,
and write AAAAH over.
(Time out of 6666H is 30 seconds.)
4. The positioning unit copies the content
of the shared memory into FROM.
5. The positioning unit checkes writing.
When OK: The unit sets 0000H.
When NG: The unit sets FFFFH.
6. When confirming 0000H by the ladder
program, the operation will be
completed successfully. When
confirming FFFFH, an error will occur.
In that case, write 0000H over in this
area.
0000H
-
-
085H
Recalculation
starting table
number
When the recalculation request signal
(Y87 contact) turns on, the positioning
unit will recalculate the positioning data
of all the axes from this table number to
No. 600.
1
1 to 600
-
17.4.3 Operation Speed Rate Area
Bank
Offset
address
Name
Descriptions
Default
value
Setting
range
Unit
00H
088H
Operation speed
rate
All operations relating to axes
(positioning, JOG, home return) can be
perfomred at the specified rate.
The unit is %, and can be input in the
range of 1 to 100 (%).
100
1 to 100
%
Summary of Contents for AFP243710
Page 16: ...xiv ...
Page 17: ...Chapter 1 Functions of Unit and Restrictions on Combination ...
Page 21: ...Chapter 2 Parts and Functions ...
Page 24: ...2 4 ...
Page 25: ...Chapter 3 Wiring ...
Page 39: ...Chapter 4 Power On Off and Items to Check ...
Page 44: ...4 6 ...
Page 45: ...Chapter 5 Preparation For Operation ...
Page 53: ...5 9 ...
Page 55: ...Chapter 6 I O Allocation ...
Page 63: ...Chapter 7 Setting Tool Configurator PM ...
Page 87: ...7 25 Setting Font Select Option Font in the menu bar The following dialog is shown ...
Page 102: ...7 40 ...
Page 103: ...Chapter 8 Automatic Operation Position Control ...
Page 115: ...8 13 ...
Page 116: ...8 14 When the X axis and Y axis is the moving axes each axis in the above diagram is replaced ...
Page 129: ...8 27 Reference Chapter 10 Manual Operation Home Return ...
Page 139: ...Chapter 9 Manual Operation JOG Operation ...
Page 144: ...9 6 ...
Page 145: ...Chapter 10 Manual Operation Home Return ...
Page 151: ...Chapter 11 Manual Operation Pulser Operation ...
Page 155: ...Chapter 12 Stop Functions ...
Page 158: ...12 4 ...
Page 159: ...Chapter 13 Supplementary Functions ...
Page 171: ...Chapter 14 Precautions During Programming ...
Page 175: ...Chapter 15 Errors and Warnings ...
Page 186: ...15 12 ...
Page 187: ...Chapter 16 Troubleshooting ...
Page 190: ...16 4 ...
Page 191: ...Chapter 17 Specifications ...
Page 241: ...Chapter 18 Dimensions ...
Page 242: ...18 2 18 1 FP2 Positioning Unit Interpolation Type 2 axis type Unit mm 4 axis type Unit mm ...
Page 243: ...Chapter 19 Sample Programs ...
Page 247: ...19 5 ...
Page 250: ...19 8 ...
Page 251: ...Chapter 20 Driver Wiring ...
Page 261: ......