13-5
13.4 Home Change
The current value update is a function to change the current value managed in the positioning unit to an
arbitrary value.
Data must be written into the shared memory from the PLC in order to carry out the current value update.
Followings are the details of the shared memory to carry out the current value update.
Home change area (Shared memory, Bank 0)
address
Name
Descriptions
0C0H
Current value
update request flag
Only when the corresponding bits for each axis changed to 1 from 0, the current
valuecooridnate managed in the positioning unit is changed to the following
current value update coordiate.
Afther the change, the positioning unit clears the corresponding bits to 0
automatically.
0C8H
Current value
update coordinate
of axis 1
Stores the coordinate to change the current value of axis 1.
0C9H
0CAH
Current value
update coordinate
of axis 2
Stores the coordinate to change the current value of axis 2.
0CBH
0CCH
Current value
update coordinate
of axis 3
Stores the coordinate to change the current value of axis 3.
0CDH
0CEH
Current value
update coordinate
of axis 4
Stores the coordinate to change the current value of axis 4.
0CFH
0D0H
Current value
update coordinate
of axis 5
Stores the coordinate to change the current value of axis 5.
0D1H
0D2H
Current value
update coordinate
of axis 6
Stores the coordinate to change the current value of axis 6.
0D3H
0D4H
Current value
update coordinate
of axis 7
Stores the coordinate to change the current value of axis 7.
0D5H
0D6H
Current value
update coordinate
of axis 8
Stores the coordinate to change the o current value of axis 8.
0D7H
Procedures of current value update
1. Write an coordinate to be the current value in the current value update coordinate area of the target
axis.
2. Write the value at the time that the bit of the target axis set to 1 in the current value request flag area.
As the current value update process is performed for the axis that is 1 in the current value request flag
area, do not set any bit to 1 other than the target axis.
3. The current value after unit conversion in each axis information and monitor area is changed to the
specified current value.
Note:
The value to be changed by updating the current value is the current value after unit
conversion.
Summary of Contents for AFP243710
Page 16: ...xiv ...
Page 17: ...Chapter 1 Functions of Unit and Restrictions on Combination ...
Page 21: ...Chapter 2 Parts and Functions ...
Page 24: ...2 4 ...
Page 25: ...Chapter 3 Wiring ...
Page 39: ...Chapter 4 Power On Off and Items to Check ...
Page 44: ...4 6 ...
Page 45: ...Chapter 5 Preparation For Operation ...
Page 53: ...5 9 ...
Page 55: ...Chapter 6 I O Allocation ...
Page 63: ...Chapter 7 Setting Tool Configurator PM ...
Page 87: ...7 25 Setting Font Select Option Font in the menu bar The following dialog is shown ...
Page 102: ...7 40 ...
Page 103: ...Chapter 8 Automatic Operation Position Control ...
Page 115: ...8 13 ...
Page 116: ...8 14 When the X axis and Y axis is the moving axes each axis in the above diagram is replaced ...
Page 129: ...8 27 Reference Chapter 10 Manual Operation Home Return ...
Page 139: ...Chapter 9 Manual Operation JOG Operation ...
Page 144: ...9 6 ...
Page 145: ...Chapter 10 Manual Operation Home Return ...
Page 151: ...Chapter 11 Manual Operation Pulser Operation ...
Page 155: ...Chapter 12 Stop Functions ...
Page 158: ...12 4 ...
Page 159: ...Chapter 13 Supplementary Functions ...
Page 171: ...Chapter 14 Precautions During Programming ...
Page 175: ...Chapter 15 Errors and Warnings ...
Page 186: ...15 12 ...
Page 187: ...Chapter 16 Troubleshooting ...
Page 190: ...16 4 ...
Page 191: ...Chapter 17 Specifications ...
Page 241: ...Chapter 18 Dimensions ...
Page 242: ...18 2 18 1 FP2 Positioning Unit Interpolation Type 2 axis type Unit mm 4 axis type Unit mm ...
Page 243: ...Chapter 19 Sample Programs ...
Page 247: ...19 5 ...
Page 250: ...19 8 ...
Page 251: ...Chapter 20 Driver Wiring ...
Page 261: ......