Install the Front Indicator Module
Servicing FRUs
161
Install the Front Indicator Module
Caution -
The front indicator module should be installed only by authorized Oracle Services
personnel.
1.
Attach an antistatic wrist strap to your wrist, and then to a metal area on the
chassis.
“Take Antistatic Measures” on page 59
2.
Unpack the replacement FIM and place it on an antistatic mat.
3.
Connect the FIM cable to the replacement FIM assembly (See
[3]).
4.
Carefully lower the FIM assembly into the chassis, position it over the
Phillips screw in the server chassis, and slide it forward so all the LEDs, USB
connectors, and Power On button fit into place on the server front panel [2].
5.
Tighten the Phillips screw to secure the FIM assembly to the server chassis [2].
6.
Position the storage drive cage cover over the server storage drive cage so that
it over hangs the front of the disk drive cage by about 1/4 inch.
7.
Install the six Phillips screws to secure the cover to the server [1].
There are three Phillips screws on each side of the storage drive cage.
8.
Close the server fan door.
9.
Return the server to operation.
a.
Return the server to the normal rack position.
“Return the Server to the Normal Rack Position” on page 191
b.
Reconnect the data cables to the server and reconnect the power cords to
the server power supplies.
“Reconnect Data Cables and Power Cords” on page 193
c.
Power on the server.
“Power On the Server” on page 194
.
Verify that the Power/OK status indicator is steady on.
Related Information
■
Summary of Contents for EXADATA X6-2
Page 1: ...Part No E62171 02 June 2016 Oracle Server X6 2 Service Manual ...
Page 2: ......
Page 12: ...12 Oracle Server X6 2 Service Manual June 2016 ...
Page 62: ...62 Oracle Server X6 2 Service Manual June 2016 ...
Page 226: ...226 Oracle Server X6 2 Service Manual June 2016 ...
Page 278: ...278 Oracle Server X6 2 Service Manual June 2016 ...
Page 284: ...284 Oracle Server X6 2 Service Manual June 2016 ...