O P E R A T I O N
91 / 192
XS20000_31_manual_ger_eng_it_V1.1.2.doc
R. Kistler
4.5
Starting and switching off the UPS system
NOTE
Before starting the UPS system, check whether all consum-
ers are switched off. After starting the UPS system, switch on
the consumers one after the other.
Switch off all consumers before switching off the UPS system.
4.5.1
Starting the UPS system with mains power supply
1. Switch the input switches MAIN 1 and MAIN 2 on the rear side
of the UPS system to the "ON" position.
The display on the front side of the UPS system lights up and
briefly displays the ONLINE logo.
2. The UPS system is in bypass mode.
3. Press the
button on the UPS system for at least one sec-
ond. An audio signal will be emitted. Several seconds later,
the UPS system will switch to normal mode. If the mains pow-
er supply is malfunctioning, the UPS system will switch to bat-
tery mode.
4.5.2
Starting the UPS system without mains power supply
NOTE
The starting in battery mode can be disabled (see
Settings
menu -
DC start).
1. Briefly press the button on the UPS system.
The display on the front side of the UPS system lights up and
briefly displays the ONLINE logo.
2. The UPS system is in standby mode.
3. Press the
button on the UPS system for at least one sec-
ond. An audio signal will be emitted. Several seconds later,
the UPS system switches to battery mode. If the mains power
supply switches on again, the UPS system will switch to nor-
mal mode without interruption.
Summary of Contents for 10000 3/1 XANTO S Series
Page 2: ...2 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 64: ...64 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 66: ...66 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 128: ...128 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 130: ...130 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 192: ...192 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...