I N S T A L L A T I O N
76 / 192
XS20000_31_manual_ger_eng_it_V1.1.2.doc
R. Kistler
Figure 4: Floor attachment
3.5
Electrical installation
NOTE
Always connect the protective earthing conductor first
Do not perform any unauthorised modifications to the UPS
system as doing otherwise will damage the system and void
the warranty
Only qualified electricians may connect the UPS system to
the power supply
3.5.1
Cable cross-section and fuses
XANTO S 10000 3/1
XANTO S 20000 3/1
Line Input / Main 1,
3~ 400V
5x 2,5mm
2
25A (3~+N)*
5x 6mm
2
40A (3~+N)*
Bypass / Main 2
(necessary), 1~ 230V
3x 10mm
2
63A (1~+N)*
3x 25mm
2
100A (1~+N)*
Output, 1~ 230V
3x 10mm
2
3x 25mm
2
Battery
3x 10mm
2
3x 10mm
2
Table 2: Cable cross-sections and fuses
* Recommended circuit breaker with characteristics C in the feed line (not included)