O P E R A T I O N
94 / 192
XS20000_31_manual_ger_eng_it_V1.1.2.doc
R. Kistler
4.7
Configuring the bypass settings
Automatic bypass:
By default, a switch to the bypass mode will be
forced if an overload occurs. You can disable the setting.
1. Press the
button for at least one second to enable the menu
options. Select "SETTINGS" and then
"AUTOMATIC
BYPASS".
2. Select "ENABLED" or "DISABLED" and press the
button
for at least one second to confirm.
3. Press the button briefly to return to the start screen.
The following settings are additionally available for configuring the
bypass mode:
Bypass voltage low limit:
By default, switching to bypass mode is
disabled if the measured bypass voltage lies below 184 V. You can
specify the settings for a different voltage value.
Bypass voltage high limit:
By default, switching to bypass mode is
disabled if the measured bypass voltage lies above 264 V. You can
specify the settings for a different voltage value.
Bypass frequency low limit:
By default, switching to bypass mode
is disabled if the measured bypass frequency lies 10% below the
nominal frequency. You can specify the setting for a different per-
centage value.
Bypass frequency high limit:
By default, switching to bypass mode
is disabled if the measured bypass frequency lies 10% above the
measured nominal frequency. You can specify the setting for a dif-
ferent percentage value.
Summary of Contents for 10000 3/1 XANTO S Series
Page 2: ...2 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 64: ...64 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 66: ...66 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 128: ...128 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 130: ...130 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 192: ...192 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...