O P E R A T I O N
96 / 192
XS20000_31_manual_ger_eng_it_V1.1.2.doc
R. Kistler
Requirements for the automatic battery test:
The "Automatic battery tests" setting may not be set to zero
The UPS system is running in normal mode and there are no
warning/error messages present
The bypass voltage is acceptable
The load is greater than 10%
No manual battery test was initiated in the same charging cycle
In order for the battery tests to pass successfully, the battery voltage
must remain above a threshold value during the discharging.
4.9
Configuring the automatic restart
After the UPS system switches off (e.g. due to flat batteries in the
event of a power failure), the UPS system is restarted by default as
soon as the power supply returns. You can disable the setting.
1. Press the
button for at least one second to enable the menu
options. Select "SETTINGS" and then
"AUTOMATIC
RESTART".
2. Select "ENABLED" or "DISABLED" and press the
button
for at least one second to confirm.
3. Press the button briefly to return to the start screen.
The following setting is additionally available:
Automatic restart overload
If the UPS system switches off due to an overload, the UPS system
will restart by default as soon as the overload is removed. You can
disable the setting.
Summary of Contents for 10000 3/1 XANTO S Series
Page 2: ...2 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 64: ...64 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 66: ...66 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 128: ...128 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 130: ...130 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 192: ...192 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...