S P E C I A L F U N C T I O N S
101 / 192
XS20000_31_manual_ger_eng_it_V1.1.2.doc
R. Kistler
5.1.3
Switching the operating mode of the UPS systems
From normal to bypass mode:
Press the
button on one of the
UPS systems for 3 seconds. All UPS systems switch to the operating
mode.
From bypass to normal mode:
Press the
button on one of the
UPS systems for one second. All UPS systems switch to the operat-
ing mode.
5.2
Converter mode
NOTE
There is no bypass function available in converter mode.
The bypass connection on the input may not be connected.
In converter mode, the UPS system always works with a specifically
defined output frequency (50 Hz or 60 Hz) regardless of which input
frequency (40 Hz to 70 Hz) is present. A fixed output frequency is
required, for example, for sensitive consumers.
1. Press the
button for at least one second to enable the menu
options. Select "SETTINGS" and then "POWER STRATEGY".
2. Select "CONVERTER" and press the
button for at least
one second to confirm.
3. Then switch to "OUTPUT FREQUENCY".
4. Select "50Hz" or "60Hz" and press the
button for at least
one second to confirm.
5. Press the button briefly to return to the start screen.
If the mains power supply is malfunctioning, the UPS system auto-
matically switches to battery mode (the frequency is maintained).
The load will be supplied as long as there is sufficient battery capaci-
ty. After the mains power supply returns, the UPS system switches
back to convertor mode.
Summary of Contents for 10000 3/1 XANTO S Series
Page 2: ...2 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 64: ...64 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 66: ...66 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 128: ...128 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 130: ...130 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 192: ...192 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...