9.
Technical Data
9.1
UPS systems specifications
9.1.1
List of the device types
UPS system
Article
number
Power
Battery
module
Article number
XANTO S 10000 3/1
XST1000031
10000 VA
9000 W
Battery module
XANTO S
10000 /
20000 3/1
XST1000031BP
XANTO S 20000 3/1
XST2000031
20000 VA
18000 W
Table 14: List of the UPS systems and battery modules
9.1.2
D
imensions and weights (net)
Dimensions (H x W x D)
Weight
XANTO S 10000 3/1
890 x 350 x 710 mm
127 kg
XANTO S 20000 3/1
890 x 350 x 710 mm
188 kg
Battery module
XANTO S 10000 / 20000 3/1
890 x 350 x 710 mm
183 kg
Table 15: Dimensions and weight
9.1.3
Electrical inputs and outputs
Nominal frequency
50 / 60Hz automatic detection
Frequency range
40 - 70 Hz before switching to battery mode
Bypass voltage range
+15 / -20% of the nominal voltage (standard)
Overvoltage protection
MOVs for normal and common
overvoltage’s
Table 16: Input power
Model
Line input
Voltage/
current
Selectable
output voltage*
Voltage range at
100% load
XANTO S 10000 3/1
400V / 3x 14A
230V / 1x 43A
200V, 208V,
220V, 230V, 240V
176 - 276 VAC
(Phase - Neutral)
XANTO S 20000 3/1
400V / 3x 28A
230V / 1x 87A
200V, 208V,
220V, 230V, 240V
176 - 276 VAC
(Phase - Neutral)
Table 17: Electrical input and output power
* At 200V output voltage, only 90% of the output power is available.
Summary of Contents for 10000 3/1 XANTO S Series
Page 2: ...2 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 64: ...64 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 66: ...66 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 128: ...128 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 130: ...130 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 192: ...192 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...