T R O U B L E S H O O T I N G
118 / 192
XS20000_31_manual_ger_eng_it_V1.1.2.doc
R. Kistler
Warning or error
message
Possible causes
Measure
Specific warning/error messages for parallel connection.
E2 Fault
Parallel Cable Fault
Parallel Cable Faulty
Check the parallel cable for cor-
rect connector contact.
E3 Warning
Parallel Cable Fault
Parallel Cable Faulty
Check the parallel cable for cor-
rect connector contact.
E4 Warning
Parallel Cable Fault
Parallel Cable Faulty
Check the parallel cable for cor-
rect connector contact.
E6 Warning
Battery Voltage Un-
balance
Different battery voltages
Check the batteries of each UPS
system These must be equal.
A battery may possibly be faulty.
E7 Warning
Three Phase Un-
balance
Different input voltages
Check the input voltages of each
UPS system.
E8 Warning
Para Byp Differ
Different bypass voltages
Check the bypass input voltages
of each UPS system.
E9 Warning
Para Work Mode
Differ
Different power strategies
Check the power strategy in the
settings of each UPS system.
EA Warning
Para Rate Power
Differ
Different UPS systems
parallel connected.
Connect only equal UPS sys-
tems together.
EB Warning
ECO In Para
ECO mode not allowed
Check the power strategy in the
settings of each UPS system.
ED Warning
CAN Commu Fail
Communication between
the UPS systems failed.
Please contact support.
Table 12: Warning/error messages
Summary of Contents for 10000 3/1 XANTO S Series
Page 2: ...2 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 64: ...64 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 66: ...66 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 128: ...128 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 130: ...130 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 192: ...192 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...