C O M M U N I C A T I O N
106 / 192
XS20000_31_manual_ger_eng_it_V1.1.2.doc
R. Kistler
6.1.3
Emergency-off function (REPO)
The emergency-off function (REPO = Remote Emergency Power-
Off) serves to shut down the UPS system and to immediately switch
off the connected consumers remotely. The REPO connector (rear
side of the UPS system) must be removed and an external emer-
gency-off switch must be connected for this.
Connection cable cross-section = 0.32 - 4 mm
2
(AWG 22 - 12)
Recommended connection cable cross-section = 1.5 mm
2
(AWG 18)
CAUTION
The emergency-off switch may not be connected to circuits
that are connected with the mains power supply network.
A reinforced insulation to the mains is required. The emer-
gency-off switch must be dimensioned for at least 24 V and
20 mA. An opening contact must be used. For proper opera-
tion, the emergency-off function must remain active for at
least 250 ms
If the emergency-off function is activated, the input voltage of
the UPS system must additionally be disconnected
NOTE
Leave the REPO connector in the emergency-off connector
plugged into the UPS system if the emergency-off function is
not required
Always test the emergency-off function before a critical load
is connected. This will prevent an unintended load breaking
Summary of Contents for 10000 3/1 XANTO S Series
Page 2: ...2 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 64: ...64 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 66: ...66 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 128: ...128 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 130: ...130 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 192: ...192 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...