6 - 5
6 Hardware Specifications of E3X-ECT
E3X-ECT EtherCAT Sensor Communication Unit Instraction Manual
6-
3 Hard
ware S
p
ec
ificat
ion
s
6
6-
3-1 S
tatus Indicator
s
It indicates the operation state.
For details on each state, refer to "5-3 Communications State Transitions" in page 5 - 4.
It indicates the information of an error.
It indicates the information of an Sensor Status.
Reference
The timing of each flashing state of indicator is as follows.
[RUN] indicator
Color
State
Contents
Green
OFF
Init state
Blinking
Pre-Operational state
Single flash
Safe-Operational state
ON
Operational state
[ERR] indicator
Color
State
Contents
Red
OFF
No error
Blinking
Communications setting error
Single flash
Synchronization error or communications data error
Double flash
Application WDT timeout
Flickering
Boot error
ON
PDI WDT timeout
[SS] indicator
Color
State
Contents
OFF
Power OFF or Initial satus of sensor connection
Green
ON
Normal
Red
ON
Sensor Error: Connecting Sensors is different form setting.
on
off
on
off
on
off
on
off
Flickering
Blinking
Single flash
Double flash
50 ms
200 ms 200 ms
200 ms
200 ms
1000 ms
200 ms 200 ms 200 ms
1000 ms
Summary of Contents for Sysmac E3X-ECT
Page 1: ...E3X ECT EtherCAT Sensor Communication Unit Operation Manual E413 E1 ...
Page 3: ......
Page 4: ...E3X ECT EtherCAT Sensor Communication Units Operation Manual Revised February 2012 ...
Page 5: ......
Page 29: ...1 EtherCAT Network 1 8 E3X ECT EtherCAT Sensor Communication Unit Instration Manual ...
Page 51: ...4 Installation and Wiring 4 12 E3X ECT EtherCAT Sensor Communication Unit Instraction Manual ...
Page 67: ...5 EtherCAT Communications 5 16 E3X ECT EtherCAT Sensor Communication Unit Instraction Manual ...
Page 137: ...A Appendix A 36 E3X ECT EtherCAT Sensor Communication Unit Instraction Manual ...
Page 139: ...Revision 2 E3X ECT EtherCAT Sensor Communication Unit Instraction Manual ...
Page 140: ......