5 Designing the Power Supply System
5 - 8
NX-series PROFINET Coupler Unit User’s Manual (W623)
Additional Information
Excess or insufficiency in the NX Unit power supply capacity can be easily checked when the
Unit configuration is created on the Edit IO Device Terminal Configuration Tab Page on the Sys-
mac Studio. Use the following procedure to check the power supply capacity.
On the Edit IO Device Terminal Configuration Tab Page on the Sysmac Studio, select the Unit
to supply NX Unit power. The power that is supplied by the NX Unit power supply (i.e., the total
power consumption) and the power supply capacity are displayed for the Supply Power/Avail-
able Power parameter. The following example is for when the PROFINET Coupler Unit is
selected.
If the power to supply exceeds the NX Unit power supply capacity of the Unit that is selected to
supply the NX Unit power, a yellow warning icon is displayed by the first NX Unit for which there
is not sufficient capacity and also by all the remaining NX Units.
However, the Sysmac Studio determines excess and insufficiency in the supplied power for an
NX Unit power supply capacity of 10 W max. It does not consider the power supply restrictions
of the NX Unit power supply in actual application conditions and IO power supply design condi-
tions. When actually designing the power supply, refer to
5-2-1 Procedure for Designing the NX
on page 5-6 and
Summary of Contents for PROFINET NX-PNC202
Page 9: ...7 NX series PROFINET Coupler Unit User s Manual W623 CONTENTS...
Page 12: ...Manual Structure 10 NX series PROFINET Coupler Unit User s Manual W623...
Page 32: ...Revision History 30 NX series PROFINET Coupler Unit User s Manual W623...
Page 34: ...Sections in this Manual 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 126: ...6 Installation 6 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 192: ...10 I O Refreshing 10 6 NX series PROFINET Coupler Unit User s Manual W623...
Page 224: ...11 PROFINET Coupler Unit Functions 11 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 260: ...12 Troubleshooting 12 36 NX series PROFINET Coupler Unit User s Manual W623...
Page 268: ...13 Maintenance and Inspection 13 8 NX series PROFINET Coupler Unit User s Manual W623...
Page 274: ...Appendices A 6 NX series PROFINET Coupler Unit User s Manual W623...
Page 275: ...I 1 I I NX series PROFINET Coupler Unit User s Manual W623 Index...
Page 280: ...I 6 NX series PROFINET Coupler Unit User s Manual W623 Index...
Page 281: ......