7 Wiring
NX-series PROFINET Coupler Unit User’s Manual (W623)
7-2 Connecting the Power Supply and Ground W
ires
7
7-2-3 Grounding the PRO
FINET
IO Device
Term
inal
If the DIN Track is made of steel and the surface is not treated to produce an insulating material, you
can omit grounding the functional ground terminal on any Unit that has one, as shown in the following
figures.
Precautions for Correct Use
• Ground the ground terminals and DIN Track through dedicated ground wires to a ground
resistance of 100 Ω or less. The ground wire should not be more than 20 m long. Use a
ground wire that is 2.0 mm
2
on page 7-12 for the applica-
ble ground wires for screwless clamping terminal blocks.
• If the DIN Track is not made of steel or if the surface is treated to produce an insulating mate-
rial
*1
, always connect ground wires to the ground terminals. Otherwise, noise may cause
malfunctions.
*1. If the surface of the DIN Track is treated to produce an insulating material (e.g., anodized aluminum), the DIN
Track contact plate will not be electrically connected to the DIN Track even if they are in physical contact.
Attach a crimped terminal to the ground wire and then connect it to mounting hole on the DIN Track with
a screw to ground the DIN Track.
Refer to
on page 6-30 for the grounding procedures for the Profinet IO Device Termi-
nal with peripheral devices and in control panels.
If the ground wire for the PROFINET Coupler Unit or an NX Unit with a ground terminal is shared with
power equipment, noise will adversely affect the Units.
You can use OMRON NX-AUX01 DIN Track Insulation Spacers with PFP-50N or PFP-100N DIN Tracks
to isolate a Profinet IO Device Terminal from the control panel.
Grounding the DIN Track
Grounding the Profinet IO Device Terminal with Peripheral Devices
and in Control Panels
Isolating the Profinet IO Device Terminal from the Control Panel
PROFINET Coupler Unit
■
DIN Track Made of Steel and Surface Not Insulated
Additional NX Unit Power Supply Unit
Functional ground terminal
Ground
DIN Track
Shield Connection Unit
Electrically connected to the DIN Track
through the DIN Track contact plate.
Functional ground terminals
End Cover
Summary of Contents for PROFINET NX-PNC202
Page 9: ...7 NX series PROFINET Coupler Unit User s Manual W623 CONTENTS...
Page 12: ...Manual Structure 10 NX series PROFINET Coupler Unit User s Manual W623...
Page 32: ...Revision History 30 NX series PROFINET Coupler Unit User s Manual W623...
Page 34: ...Sections in this Manual 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 126: ...6 Installation 6 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 192: ...10 I O Refreshing 10 6 NX series PROFINET Coupler Unit User s Manual W623...
Page 224: ...11 PROFINET Coupler Unit Functions 11 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 260: ...12 Troubleshooting 12 36 NX series PROFINET Coupler Unit User s Manual W623...
Page 268: ...13 Maintenance and Inspection 13 8 NX series PROFINET Coupler Unit User s Manual W623...
Page 274: ...Appendices A 6 NX series PROFINET Coupler Unit User s Manual W623...
Page 275: ...I 1 I I NX series PROFINET Coupler Unit User s Manual W623 Index...
Page 280: ...I 6 NX series PROFINET Coupler Unit User s Manual W623 Index...
Page 281: ......