![Omron PROFINET NX-PNC202 User Manual Download Page 90](http://html1.mh-extra.com/html/omron/profinet-nx-pnc202/profinet-nx-pnc202_user-manual_742786090.webp)
5 Designing the Power Supply System
5 - 18
NX-series PROFINET Coupler Unit User’s Manual (W623)
Precautions for Correct Use
Consider the inrush current when the power supply is turned ON and select a Unit power sup-
ply with sufficient extra capacity. The inrush current when power is turned ON may prevent the
Unit power supply from operating correctly.
This section describes how to select the IO power supplies for the Profinet IO Device Terminal.
Use an SELV power supply that meets the following conditions for the IO power supply.
• Has overcurrent protection.
• Has double or reinforced insulation between the input and output.
• Has an output voltage of 5 to 24 VDC (4.5 to 28.8 VDC).
*1. Use an output voltage that is appropriate for the IO circuits of the NX Units and the connected external
devices.
Recommended Power Supplies: S8JX Series (manufactured by OMRON)
Use the calculation method that is described in
5-3 Designing the IO Power Supply System
and calculate the total current consumption from the IO power supply and the required power supply
capacity of the IO power supply.
Unlike the Unit power supply, it is not necessary to use only one IO power supply to supply power to the
entire IO Device Terminal.
Precautions for Correct Use
Consider the inrush current when the power supply is turned ON and select an IO power supply
with sufficient extra capacity. The inrush current when power is turned ON may prevent the IO
power supply from operating correctly.
This section describes how to select protective devices (e.g., breakers and fuses) to protect against
short circuits and overcurrents in external circuits.
Overcurrent is the current that flows when an excessive load is connected and one of the following rat-
ings is exceeded.
• For the Unit power supply, the rating of the NX Unit power supply capacity or of the current capacity
of the power supply terminals
• For the IO power supply, the rating of the maximum IO power supply current or of the current capacity
of the power supply terminals
For the above ratings for the PROFINET Coupler Unit, refer to
3-1-3 PROFINET Coupler Unit Specifi-
on page 3-4. For the ratings of NX-series power supply-related Units, refer to the
NX-series
System Units User’s Manual
(Cat. No. W523).
5-4-2 Selecting the IO Power Supplies
Recommended Power Supplies
Calculating the Required Power Supply Capacity of the IO Power
Supply
5-4-3 Selecting Protective Devices
Summary of Contents for PROFINET NX-PNC202
Page 9: ...7 NX series PROFINET Coupler Unit User s Manual W623 CONTENTS...
Page 12: ...Manual Structure 10 NX series PROFINET Coupler Unit User s Manual W623...
Page 32: ...Revision History 30 NX series PROFINET Coupler Unit User s Manual W623...
Page 34: ...Sections in this Manual 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 126: ...6 Installation 6 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 192: ...10 I O Refreshing 10 6 NX series PROFINET Coupler Unit User s Manual W623...
Page 224: ...11 PROFINET Coupler Unit Functions 11 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 260: ...12 Troubleshooting 12 36 NX series PROFINET Coupler Unit User s Manual W623...
Page 268: ...13 Maintenance and Inspection 13 8 NX series PROFINET Coupler Unit User s Manual W623...
Page 274: ...Appendices A 6 NX series PROFINET Coupler Unit User s Manual W623...
Page 275: ...I 1 I I NX series PROFINET Coupler Unit User s Manual W623 Index...
Page 280: ...I 6 NX series PROFINET Coupler Unit User s Manual W623 Index...
Page 281: ......