![Omron PROFINET NX-PNC202 User Manual Download Page 250](http://html1.mh-extra.com/html/omron/profinet-nx-pnc202/profinet-nx-pnc202_user-manual_742786250.webp)
12 Troubleshooting
12 - 26
NX-series PROFINET Coupler Unit User’s Manual (W623)
Event name
NX Unit Initialization Error
Event code
84C10000 hex
Meaning
Initializing an NX Unit failed.
Source
Build-in Ethernet port
Source details
Communica-
tions Coupler
Unit
Detection
timing
When power is
turned ON to
the Communi-
cations Cou-
pler Unit, the IO
Device Termi-
nal is restarted,
an NX Unit is
restarted, or an
error is reset in
the Communi-
cations Cou-
pler Unit
Error
attributes
Level
Minor fault
Recovery
Reset error in
Communica-
tions Coupler
Unit.
Log category
System
Effects
User program
Continues.
Operation
When Fail-soft Operation Is Set to
Fail-soft
• Communications Coupler Unit, NX Bus
IO refreshing for all of the NX Units that have an
initialization error in the IO Device Terminal stops.
When Fail-soft Operation Is Set to
Stop
• Communications Coupler Unit, PROFINET Com-
munications
Ethernet communication stops.
• Communications Coupler Unit, NX Bus
IO refreshing for the NX Units in the IO Device Ter-
minal stops.
Sys-
tem-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
An error occurred in processing
the Communication Coupler Unit.
Set and save the Unit configura-
tion information in the Communi-
cation Coupler Unit again.
If this error occurs again, check
that there are no errors in the NX
Unit settings and IO data mapping
information, and correct any errors
that are found.
Correctly set NX Units and IO data
mapping information, and set and
save the Unit configuration infor-
mation in the Communication
Coupler Unit.
An initialization error occurred in
an NX Unit.
Cycle the power supply to the rel-
evant NX Unit.
If the error occurs again, replace
the NX Unit.
None
The Channel Enable/Disable Set-
ting for all channels of the Analog
Input Unit are set to
Disable
.
The Enabled Channel Settings for
all channels of the Analog Output
Unit are set to
Disable
.
Set the Enabled Channel Setting
to
Enable
for at least one channel.
Set the Enabled Channel Setting
to
Disabled
for only the unused
channels.
Attached
information
Attached information 1: Unit number of the NX Unit where the error was detected
Precautions/
Remarks
None
Summary of Contents for PROFINET NX-PNC202
Page 9: ...7 NX series PROFINET Coupler Unit User s Manual W623 CONTENTS...
Page 12: ...Manual Structure 10 NX series PROFINET Coupler Unit User s Manual W623...
Page 32: ...Revision History 30 NX series PROFINET Coupler Unit User s Manual W623...
Page 34: ...Sections in this Manual 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 126: ...6 Installation 6 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 192: ...10 I O Refreshing 10 6 NX series PROFINET Coupler Unit User s Manual W623...
Page 224: ...11 PROFINET Coupler Unit Functions 11 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 260: ...12 Troubleshooting 12 36 NX series PROFINET Coupler Unit User s Manual W623...
Page 268: ...13 Maintenance and Inspection 13 8 NX series PROFINET Coupler Unit User s Manual W623...
Page 274: ...Appendices A 6 NX series PROFINET Coupler Unit User s Manual W623...
Page 275: ...I 1 I I NX series PROFINET Coupler Unit User s Manual W623 Index...
Page 280: ...I 6 NX series PROFINET Coupler Unit User s Manual W623 Index...
Page 281: ......