7 - 7
7 Wiring
NX-series PROFINET Coupler Unit User’s Manual (W623)
7-2 Connecting the Power Supply and Ground W
ires
7
7-2-2 W
iring the Power Supply to the PROFINET
IO Device
Ter-
minal
Functional Ground Terminals
These are the functional ground terminals. Connect the ground wire to one of these terminals. The
details are given in the following table.
Precautions for Correct Use
Do not connect the through-wiring terminals on the Unit power supply terminals to the IO power
supply terminals. Always use separate power supplies for the Unit power supply and the IO
power supply. Otherwise, noise may cause malfunctions.
7-2-5 Wiring to the Screwless Clamping Terminal Block
on page 7-11 for the procedure to
connect wires to the terminals on the screwless clamping terminal block.
Refer to
Section 5 Designing the Power Supply System
for information on wiring the power supplies to
the Profinet IO Device Terminal.
This section describes how to ground the Profinet IO Device Terminal.
Some of the Units in a Profinet IO Device Terminal have ground terminals.
Units with Ground Terminals
• PROFINET Coupler Units
• Additional NX Unit Power Supply Unit
• Shield Connection Unit
When connecting NX Units to external devices, the Shield Connection Unit is used to connect
the shield wire when the shield is used. You can ground more than one shield wire to the same
ground pole to reduce the amount of wiring work for grounding. For the specifications of the
Shield Connection Unit, refer to the
NX-series System Units User’s Manual
(Cat. No. W523).
Type of Ground Terminals
The ground terminals are functional ground terminals.
Functional grounding is done to protect device and system functions, including prevention of noise
from external sources, or prevention of noise from devices or equipment that could have harmful
effects on other devices or equipment.
Terminal number indication
Terminal symbol
Description
A7 or B7
Connect the ground wire to either the A7 or B7 ter-
minal.
7-2-2 Wiring the Power Supply to the PROFINET IO Device Terminal
7-2-3 Grounding the PROFINET IO Device Terminal
Units with Ground Terminals and Type of Ground Terminals
Summary of Contents for PROFINET NX-PNC202
Page 9: ...7 NX series PROFINET Coupler Unit User s Manual W623 CONTENTS...
Page 12: ...Manual Structure 10 NX series PROFINET Coupler Unit User s Manual W623...
Page 32: ...Revision History 30 NX series PROFINET Coupler Unit User s Manual W623...
Page 34: ...Sections in this Manual 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 126: ...6 Installation 6 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 192: ...10 I O Refreshing 10 6 NX series PROFINET Coupler Unit User s Manual W623...
Page 224: ...11 PROFINET Coupler Unit Functions 11 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 260: ...12 Troubleshooting 12 36 NX series PROFINET Coupler Unit User s Manual W623...
Page 268: ...13 Maintenance and Inspection 13 8 NX series PROFINET Coupler Unit User s Manual W623...
Page 274: ...Appendices A 6 NX series PROFINET Coupler Unit User s Manual W623...
Page 275: ...I 1 I I NX series PROFINET Coupler Unit User s Manual W623 Index...
Page 280: ...I 6 NX series PROFINET Coupler Unit User s Manual W623 Index...
Page 281: ......