9 Setting Up the PROFINET Coupler Unit
9 - 24
NX-series PROFINET Coupler Unit User’s Manual (W623)
NX Unit IO Data Active Status
NX Unit Error Status
*1. This applies when only the physical Unit configuration information is used and the Unit configuration informa-
tion is not registered.
Data name
Description
NX Unit IO Data Active Sta-
tus 63
This status tells whether the NX Units can process IO data communications.
The status is acquired for as many NX Units as the numeric suffix at the end of
the data name. Select the IO data with the appropriate numeric value based on
the number of NX Units that are mounted.
This status is given as an array of BOOL data. The subscript of the array corre-
sponds to the NX Unit number. A subscript of 0 indicates the PROFINET Coupler
Unit.
Each bit has the following meaning.
TRUE: The IO data in the NX Unit can be used for control.
FALSE: The IO data in the NX Unit cannot be used for control.
The status is FALSE for NX Units that are set as unmounted Units.
Each bit is updated when the operating status changes on the corresponding NX
Unit
Data name
Description
NX Unit Error Status 63
This status tells whether an error exists on the NX Units.
The status is acquired for as many NX Units as the numeric suffix at the end of
the data name. Select the IO data with the appropriate numeric value based on
the number of NX Units that are mounted.
This status is given as an array of BOOL data. The subscript of the array corre-
sponds to the NX Unit number. A subscript of 0 indicates the PROFINET Coupler
Unit.
Each bit has the following meaning.
TRUE: Error
FALSE: No error
If the Unit configuration information is registered, the status is reported for only
the NX Units for which the NX Unit Registration Status is TRUE (registered). This
status is FALSE for all NX Units for which the NX Unit Registration Status is
FALSE (not registered). If automatic generation
*1
is used for the Unit configura-
tion information, the status is given for all NX Units.
Each bit is set to TRUE when the level of the error is as follows:
• Minor fault
• Observation
The status is FALSE for NX Units that are set as unmounted Units.
Each bit is updated at the following times.
The status changes to TRUE when an error occurs.
The status changes to FALSE when the error is reset. Even if the cause of the
error has been removed, you must reset the error for the status to change to
FALSE.
Summary of Contents for PROFINET NX-PNC202
Page 9: ...7 NX series PROFINET Coupler Unit User s Manual W623 CONTENTS...
Page 12: ...Manual Structure 10 NX series PROFINET Coupler Unit User s Manual W623...
Page 32: ...Revision History 30 NX series PROFINET Coupler Unit User s Manual W623...
Page 34: ...Sections in this Manual 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 126: ...6 Installation 6 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 192: ...10 I O Refreshing 10 6 NX series PROFINET Coupler Unit User s Manual W623...
Page 224: ...11 PROFINET Coupler Unit Functions 11 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 260: ...12 Troubleshooting 12 36 NX series PROFINET Coupler Unit User s Manual W623...
Page 268: ...13 Maintenance and Inspection 13 8 NX series PROFINET Coupler Unit User s Manual W623...
Page 274: ...Appendices A 6 NX series PROFINET Coupler Unit User s Manual W623...
Page 275: ...I 1 I I NX series PROFINET Coupler Unit User s Manual W623 Index...
Page 280: ...I 6 NX series PROFINET Coupler Unit User s Manual W623 Index...
Page 281: ......