5 - 13
5 Designing the Power Supply System
NX-series PROFINET Coupler Unit User’s Manual (W623)
5-3 Designing the IO Pow
er Supply System
5
5-3-2 Designing the IO Power Supply from the NX Bus
*1. The current consumption of the PROFINET Coupler Unit is not actually 0 A. However, a value of 0 A is used
in this calculation example.
In actual calculations, use the current consumption from the IO power supply that is given elsewhere in this
manual.
Outline
Find the IO power supply voltage of the NX Unit that is the farthest from the PROFINET Coupler
Unit. In this example, the IO power supply voltage of Unit (7) is found.
Conditions
Assume that an IO power supply voltage of 24.00 VDC is supplied to the IO power supply terminals
on the PROFINET Coupler Unit.
Procedure
1
Use the following formula to calculate the total current consumption from the IO power supply.
2
Find the IO power supply voltage and make sure that it is within the voltage specifications of the
IO circuits of the NX Units and the connected external devices.
If the IO power supply voltages of the connected external devices are different, connect an Additional
IO Power Supply Unit at the point where the IO power supply voltage changes and then perform similar
calculations to design a system that meets the power supply conditions. The same method is used to
separate the power supply systems. Connect an Additional IO Power Supply Unit at the point where the
Total current consumption from the IO power supply =(1) + (2) + (3) + (4) + (5) + (6) + (7)
= 0 A + 1.5 A + 1.5 A + 0 A + 0 A + 0.5 A + 0.5 A
= 4 A
IO power supply voltage at (7) = IO power supply voltage on IO power supply terminals − (Voltage drop per Unit ×
Number of Units passed through)
= 24.00 V − 0.08 V × (7 − 1 Units)
= 23.52 V
Design to Separate the IO Power Supply
Example:
(1)
(2)
(2)
(4)
(5)
(6)
(7)
To external
devices
To external
devices
I/O power
supply
(24 VDC)
Power Consumption of Individual Units
(1): 0 A
*1
(Supplied from the NX bus.)
(2) and (3): 1.5 A each (Supplied from the NX bus.)
(4) and (5): 0 A (Supplied from external source.)
(6) and (7): 0.5 A each (Supplied from the NX bus.)
● Total current consumption from the Units
that are supplied I/O power from the
PROFINET
Coupler Unit (total for (1)
to (7) = 4 A)
● Units that are supplied I/O
power from the Additional I/O
Power Supply Unit
Additional I/O Power Supply Unit
PROFINET
Coupler
NX Units
End Cover
To external
devices
I/O power
supply
(24 VDC)
Summary of Contents for PROFINET NX-PNC202
Page 9: ...7 NX series PROFINET Coupler Unit User s Manual W623 CONTENTS...
Page 12: ...Manual Structure 10 NX series PROFINET Coupler Unit User s Manual W623...
Page 32: ...Revision History 30 NX series PROFINET Coupler Unit User s Manual W623...
Page 34: ...Sections in this Manual 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 126: ...6 Installation 6 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 192: ...10 I O Refreshing 10 6 NX series PROFINET Coupler Unit User s Manual W623...
Page 224: ...11 PROFINET Coupler Unit Functions 11 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 260: ...12 Troubleshooting 12 36 NX series PROFINET Coupler Unit User s Manual W623...
Page 268: ...13 Maintenance and Inspection 13 8 NX series PROFINET Coupler Unit User s Manual W623...
Page 274: ...Appendices A 6 NX series PROFINET Coupler Unit User s Manual W623...
Page 275: ...I 1 I I NX series PROFINET Coupler Unit User s Manual W623 Index...
Page 280: ...I 6 NX series PROFINET Coupler Unit User s Manual W623 Index...
Page 281: ......