![Omron PROFINET NX-PNC202 User Manual Download Page 245](http://html1.mh-extra.com/html/omron/profinet-nx-pnc202/profinet-nx-pnc202_user-manual_742786245.webp)
12 - 21
12 Troubleshooting
NX-series PROFINET Coupler Unit User’s Manual (W623)
12-3 Checking for Errors and T
roubleshooting with Sysm
ac Studio
12
12-3-4 Event Codes for Errors and
Troubleshooting Procedures
Event name
Unit Configuration Verification Error
Event code
35010000 hex
Meaning
There is an inconsistency between the Unit configuration information in the Communication Coupler Unit
and the Units that are actually connected. Or, the Unit configuration was changed during operation while the
Unit configuration information was not set in the Communication Coupler Unit.
Source
Build-in Ethernet port
Source details
Communica-
tions Coupler
Unit
Detection
timing
When power is
turned ON to
the Communi-
cations Cou-
pler Unit, when
the IO Device
Terminal is
restarted, or
during NX bus
communica-
tions
Error
attributes
Level
Minor fault
Recovery
Cycle power to
the Communi-
cations Cou-
pler Unit or
restart the IO
Device Termi-
nal.
Log category
System
Effects
User program
Continues.
Operation
When Fail-soft Operation Is Set to
Fail-soft
and
Fail-soft Operation Is Possible
• Communications Coupler Unit, NX Bus
IO refreshing for the NX Units that have a verifica-
tion error in the IO Device Terminal stops.
Messages cannot be sent to the NX Units that
have a verification error in the IO Device Terminal.
When Fail-soft Operation Is Set to
Fail-soft
and
Fail-soft Operation Is Not Possible
The operation is the same as when fail-soft opera-
tion is set to
Stop.
When Fail-soft Operation Is Set to
Stop
• Communications Coupler Unit, PROFINET Com-
munications
Ethernet communications stops.
• Communications Coupler Unit, NX Bus
IO refreshing for the NX Units in the IO Device Ter-
minal stops.
Messages cannot be sent to the NX Units in the IO
Device Terminal.
Sys-
tem-defined
variables
Variable
Data type
Name
None
---
---
Summary of Contents for PROFINET NX-PNC202
Page 9: ...7 NX series PROFINET Coupler Unit User s Manual W623 CONTENTS...
Page 12: ...Manual Structure 10 NX series PROFINET Coupler Unit User s Manual W623...
Page 32: ...Revision History 30 NX series PROFINET Coupler Unit User s Manual W623...
Page 34: ...Sections in this Manual 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 126: ...6 Installation 6 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 192: ...10 I O Refreshing 10 6 NX series PROFINET Coupler Unit User s Manual W623...
Page 224: ...11 PROFINET Coupler Unit Functions 11 32 NX series PROFINET Coupler Unit User s Manual W623...
Page 260: ...12 Troubleshooting 12 36 NX series PROFINET Coupler Unit User s Manual W623...
Page 268: ...13 Maintenance and Inspection 13 8 NX series PROFINET Coupler Unit User s Manual W623...
Page 274: ...Appendices A 6 NX series PROFINET Coupler Unit User s Manual W623...
Page 275: ...I 1 I I NX series PROFINET Coupler Unit User s Manual W623 Index...
Page 280: ...I 6 NX series PROFINET Coupler Unit User s Manual W623 Index...
Page 281: ......