4 Safety Function Blocks
4 - 10
NX-series Safety Control Unit Instructions Reference Manual (Z931)
• This FB monitors the time that two SAFEBOOL inputs are the same and outputs the result on the
SAFEBOOL output when they are different.
•
S_ChannelNC
and
S_ChannelNO
are dependent on each other. The evaluation result for both chan-
nels is output.
• When the input for one channel changes so that the two channel inputs are no longer different, the
FB starts monitoring the discrepancy time. An error occurs if a change does not occur that makes
them different again within the monitoring time.
• If
S_AntivalentOut
is TRUE and the signal for one channel changes, the output immediately changes
to FALSE.
• If an error occurs, make the inputs for both channels inactive (make
S_ChannelNC
FALSE and make
S_ChannelNO
TRUE) to reset the FB.
• Set
DiscrepancyTime
to a value that is longer than the safety task period.
Refer to the
NX-series Safety Control Unit User’s Manual
(Cat. No. Z930) for application methods for
DiscrepancyTime
.
Precautions for Correct Use
This FB does not have a restart interlock. You must connect it to a FB that has a restart inter-
lock.
Function
Summary of Contents for NX-SL series
Page 8: ...CONTENTS 6 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Page 28: ...Sections in this Manual 26 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Page 98: ...2 Standard Functions 2 64 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Page 104: ...2 Standard Functions 2 70 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Page 110: ...2 Standard Functions 2 76 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Page 265: ...I 1 I NX series Safety Control Unit Instructions Reference Manual Z931 Index ...
Page 268: ...I 4 NX series Safety Control Unit Instructions Reference Manual Z931 Index ...
Page 269: ......