4 Safety Function Blocks
4 - 14
NX-series Safety Control Unit Instructions Reference Manual (Z931)
8004
32772
Wait for NO
S_ChannelNC
changed to TRUE, the discrepancy time timer
started operation, and the FB is waiting for
S_ChannelNO
to
change to FALSE.
Ready
= TRUE
S_AntivalentOut
= FALSE
Error
= FALSE
8014
32788
Wait for NC
S_ChannelNO
changed to FALSE, the discrepancy time
timer started operation, and the FB is waiting for
S_ChannelNC
to change to TRUE.
Ready
= TRUE
S_AntivalentOut
= FALSE
Error
= FALSE
8005
32773
From Active
Wait
One of the channels changed to FALSE, the discrepancy
time timer started operation, and the FB is waiting for the
other channel to change to FALSE.
Ready
= TRUE
S_AntivalentOut
= FALSE
Error
= FALSE
DiagCode (hexadecimal)
DiagCode
(decimal)
Status name
Status description and output results
Summary of Contents for NX-SL series
Page 8: ...CONTENTS 6 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Page 28: ...Sections in this Manual 26 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Page 98: ...2 Standard Functions 2 64 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Page 104: ...2 Standard Functions 2 70 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Page 110: ...2 Standard Functions 2 76 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Page 265: ...I 1 I NX series Safety Control Unit Instructions Reference Manual Z931 Index ...
Page 268: ...I 4 NX series Safety Control Unit Instructions Reference Manual Z931 Index ...
Page 269: ......