4 Safety Function Blocks
4 - 48
NX-series Safety Control Unit Instructions Reference Manual (Z931)
8004
32772
Wait for S_ESPE_In 2
The FB is active. A safety request was detected.
Make sure that
Reset
is FALSE. The FB is waiting
for
S_ESPE_In
to change to TRUE.
Ready
= TRUE
S_ESPE_Out
= FALSE
Error
= FALSE
8005
32773
Wait for Reset 2
The FB is active.
S_ESPE_In
is TRUE
.
Check
S_AutoReset.
Or, the FB is waiting for
Reset
to
change to TRUE.
Ready
= TRUE
S_ESPE_Out
= FALSE
Error
= FALSE
8000
32768
Safety Output Enabled
The FB is active.
S_ESPE_In
is TRUE
and
S_ESPE_Out
is TRUE (function mode).
Ready
= TRUE
S_ESPE_Out
= TRUE
Error
= FALSE
DiagCode (hexadecimal)
DiagCode
(decimal)
Status name
Status description and output results