4 Safety Function Blocks
4 - 106
NX-series Safety Control Unit Instructions Reference Manual (Z931)
FB-specific State Codes (No Error)
DiagCode (hexadecimal)
DiagCode
(decimal)
Status name
Status description and output results
0000
0
Idle
The FB is disabled (default).
Ready
= FALSE
S_OutControl
= FALSE
Error
= FALSE
8001
32769
Init
Activate
is set to TRUE and the FB is activated.
S_StartReset
is ON. Resetting is required.
Ready
= TRUE
S_OutControl
= FALSE
Error
= FALSE
8002
32770
Safe
S_SafeControl
changed to OFF, so
S_OutControl
changed to OFF.
Ready
= TRUE
S_OutControl
= FALSE
Error
= FALSE
8003
32771
Lock
S_SafeControl
changed to ON and
S_AutoReset
changed to OFF, so the FB is waiting for a
Reset
input.
Ready
= TRUE
S_OutControl
= FALSE
Error
= FALSE
8010
32784
Output Disable
ProcessControl
is OFF.
Ready
= TRUE
S_OutControl
= FALSE
Error
= FALSE
8000
32768
Output Enable
ProcessControl
is ON.
Ready
= TRUE
S_OutControl
= TRUE
Error
= FALSE
Summary of Contents for NX-SL series
Page 8: ...CONTENTS 6 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Page 28: ...Sections in this Manual 26 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Page 98: ...2 Standard Functions 2 64 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Page 104: ...2 Standard Functions 2 70 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Page 110: ...2 Standard Functions 2 76 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Page 265: ...I 1 I NX series Safety Control Unit Instructions Reference Manual Z931 Index ...
Page 268: ...I 4 NX series Safety Control Unit Instructions Reference Manual Z931 Index ...
Page 269: ......