4 - 37
4 Safety Function Blocks
NX-series Safety Control Unit Instructions Reference Manual (Z931)
4
SF
_Equivalent
• This FB monitors the time that two equivalent SAFEBOOL inputs are not the same and converts the
inputs to one SAFEBOOL output.
•
S_ChannelA
and
S_ChannelB
are dependent on each other. The evaluation result for both channels
is output.
• When the input for one channel changes so that the two channel inputs are no longer the same, the
FB starts monitoring the discrepancy time. An error occurs if a change does not occur that makes
them the same again within the monitoring time.
•
S_EquivalentOut
is TRUE if the conditions for both changes are met and FALSE if the conditions are
not met.
• If an error occurs, make the inputs for both channels inactive (make
S_ChannelA
and
S_ChannelA
FALSE) to reset the FB.
• Set
DiscrepancyTime
to a value that is longer than the safety task period.
Refer to the
NX-series Safety Control Unit User’s Manual
(Cat. No. Z930) for application methods for
DiscrepancyTime
.
Precautions for Correct Use
This FB does not have a restart interlock. You must connect it to a FB that has a restart inter-
lock.
Function
Summary of Contents for NX-SL series
Page 8: ...CONTENTS 6 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Page 28: ...Sections in this Manual 26 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Page 98: ...2 Standard Functions 2 64 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Page 104: ...2 Standard Functions 2 70 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Page 110: ...2 Standard Functions 2 76 NX series Safety Control Unit Instructions Reference Manual Z931 ...
Page 265: ...I 1 I NX series Safety Control Unit Instructions Reference Manual Z931 Index ...
Page 268: ...I 4 NX series Safety Control Unit Instructions Reference Manual Z931 Index ...
Page 269: ......