Hysteresis
The established set value includes a hysteresis to prevent the comparative
output status from tuning ON/OFF when it should not if the process value
(displayed value) fluctuates in the vicinity of the established set value.
Setting range
to
RUN mode
Press and hold the Level Key for 2 seconds to select level 1.
Setting level 1
Press the Display Key.
LED Models
Thumbwheel Switches Models
Press and hold the Level Key for
1 second to return to RUN mode.
Press the Up Key and Shift Key to set the hysteresis value and press the
Display Key to write the value.
Press the Shift Key several times to display
.
H comparative output
L comparative output
L set value
Hysteresis
H set value
Logically, 0 cannot be set as a hysteresis value. If 0 is set, the K3TS takes
the hysteresis value as 1. If sampling hold, maximum hold, minimum hold,
peak-to-peak hold values are set on operating parameter 3 (on setting level
3), no hysteresis setting is available.
! $